If you have an old expansion and want to request a replacement, the first thing you will likely look at is the size of the connection. The size tells you how the valve will fit onto the pipes, and its capacity is determined by other data, the most important of which are the type of refrigerant, the load of the evaporator, the evaporation temperature, and the available pressure drop across the valve. That's why two valves with the same connections can operate at different capacities.
What does the expansion do inside the circuit?
Thermal expansion valve (TXV) regulates the amount of refrigerant entering the evaporator. The bulb mounted on the suction line at the evaporator outlet senses the line temperature, and the valve responds to changes in superheat. Superheat is the difference between the vapor temperature at the evaporator outlet and the saturation temperature corresponding to its pressure at the same location. When superheat increases, the valve tends to open more, and when it decreases, the valve reduces the feed.
What is the difference between the valve body and the orifice?
In models like Danfoss T2 and TE2, the orifice is a changeable piece that determines the valve capacity under operating conditions. The selection is done in two steps. First, you determine the valve body suitable for the refrigerant and type of balancing. Then you choose the orifice from the capacity table according to the actual load and operating conditions. When you request an “expansion with orifice,” ask for both codes together to clarify what will be delivered to you.
When does internal and external balancing matter?
Balancing determines where the valve takes the evaporator pressure from. In the internal type, the valve uses the pressure at its outlet. In the external type, a separate balancing line transmits the suction line pressure at the evaporator outlet. The difference is important when there is a noticeable pressure drop between the two points, like some evaporators that have a refrigerant distributor. If the evaporator has a distributor, refer to the manufacturer's instructions to determine the required type of balancing.
What data do you need to request before choosing the expansion?
| Data | What does it affect? |
|---|---|
| Type of refrigerant | Choosing the valve body and reading the capacity table for the refrigerant. |
| Evaporator capacity in kilowatts at design conditions | Determining the required capacity from the valve and orifice. |
| Evaporation temperature | Determining the operating point in the selection table. Room temperature alone is not sufficient for its calculation. |
| Condensation conditions and liquid temperature at the valve inlet | It affects the calculation of the available pressure drop and the correction of capacity according to the manufacturer's data. |
| Presence of a distributor and type of balancing | Determining the type of valve body and considering the pressure drop across the distributor. |
| Connection sizes and type | Ensuring compatibility of the installation, whether the connections are flare or welded according to the model. |
The orifice capacity in the catalog is related to measurement conditions. Use the manufacturer's selection table or program with actual system data, and review Net pressure drop across the valve after calculating the relevant losses in the liquid line and distributor according to the circuit design.
A practical example from a freezing room at −18°C
You have an evaporator with a capacity of 6 kilowatts at design conditions, and the unit operates with R404A, and the evaporator has a distributor. If you ask the supplier for "Expansion for a room at −18°C", you still need to provide them with the design evaporation temperature and the condensation and liquid data. Then they can determine the appropriate valve body and balancing type, and choose an orifice that covers the 6 kilowatt load at these operating conditions. The number here is for illustration, and the orifice code is determined from the model table.
If you are going to change an existing valve, what do you send to the supplier?
Take a picture of the valve body code, and the orifice number if known, and the data plate of the evaporator or unit.. If the work involves changing the refrigerant or replacing the evaporator, send the modification data so that the selection can be reviewed based on the new operating conditions.
Are you looking for an expansion or alternative orifice? Send the images and codes to the team Bassem for Refrigeration Industries so we can help you match the specifications before ordering. Writing from here...