If the freezer reaches −18°F, after the defrost, and after a few hours the temperature rises and the air coming from the evaporator weakens, focus on two questions: Where did the ice appear first? And when did it return? The answer helps the technician determine whether to start from the defrost cycle, or drainage, or the entry of humid air during loading.
When is frost considered normal?
When humid air passes over the cold evaporator fins, moisture can freeze on them. That's why a light layer of frost before defrosting, or the defrost cycle, can be part of normal operation. The problem starts when the ice remains after the cycle, or accumulates to the point that it blocks the gaps between the fins. At that time, the air passing over the evaporator decreases, and the room may take longer to reach the desired temperature.
The location of the ice and the timing of its appearance guide the inspection
| that you observe | The first thing the technician reviews |
|---|---|
| Is there still ice between the fins after the defrost ends? | Has the defrost cycle completed? In the electrical system, check the heaters and the defrost end sensor and control settings. |
| Ice appears in the drain pan or around the drain opening. | Is the defrost water coming out of the pan? Check for drain blockage and the drain line heater if the system is equipped with one. |
| The evaporator comes out clean after defrosting, but frost increases quickly after loading. | The duration of door opening, the condition of the door seal, and the entry of humid air during receiving. |
| The airflow is weak even after the ice has melted. | Running the evaporator fans after the delay period, the cleanliness of the fins, and the presence of boxes or goods in front of the airflow path. |
These signs determine the starting point of the inspection. For example, the fans stopping during the defrost or for a short period after it could be part of the control method. If they remain off after the delay period and the cooling request resumes, the technician reviews the operation order, power supply, and motor.
A practical example from a freezing room receiving a daily shipment.
Imagine that the same room works well in the morning, and after receiving the afternoon shipment, the airflow weakens and the temperature starts to rise. If the evaporator was clean after the defrost and frost increased with the door opening, the inspection starts from the entry of humid air during loading.. If the ice was already present before the shipment arrived and remained between the fins after the defrost, the inspection starts from the completion of the defrost cycle.. In both cases, the timing of the problem gives the technician information more important than just the image of the ice.
What should you record before the technician's visit?
- The required and actual room temperature. The time the problem appeared.
- A picture of the evaporator before and after the defrost. It shows the location of the ice.
- The time of the last defrost and the time the ice returned,, and whether it coincided with loading or opening the door.
- The condition of the fans after the cooling resumes. And any alarm code that appeared on the control.
Is ice returning on the evaporator of the freezing room? Send to the team Bassem for Refrigeration Industries. Pictures of the evaporator and operating data so we can help you determine where to start the inspection.