EK-DI-263AC10-A08 C
30.70 kW
Defrost: None
Product code: EK-DI-163AI10-A08 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 15,103 m³/h |
|---|---|
| External surface | 132.0 m² |
| Inner volume | 54.0 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 285 kg |
| Quantity | 1 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 1,900 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 69.0 dB(A) |
|---|---|
| Sound power | 92.0 dB(A) |
| Energy class | C |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø54 |
| EK-DI-163AI10-A08 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 13.89 | 13.70 | 13.59 | 13.54 | 13.44 | 13.30 | 13.13 | 13.20 | 13.99 | 15.11 | 14.70 | 14.56 | 14.37 | 14.06 |
| 5 | 15.95 | 15.90 | 15.91 | 17.72 | 17.65 | 17.51 | 17.30 | 17.33 | 18.34 | 19.79 | 19.19 | 18.97 | 18.66 | 18.19 |
| 6 | 19.38 | 19.52 | 19.68 | 22.05 | 22.04 | 21.93 | 21.72 | 21.72 | 22.97 | 24.77 | 23.98 | 23.68 | 23.25 | 22.56 |
| 7 | 22.60 | 23.01 | 23.40 | 26.38 | 26.53 | 26.49 | 26.29 | 26.28 | 27.79 | 29.99 | 29.01 | 28.62 | 28.05 | 27.11 |
| 8 | 25.64 | 26.37 | 27.04 | 30.58 | 30.92 | 31.00 | 30.89 | 30.92 | 32.71 | 35.31 | 34.17 | 33.70 | 33.01 | 31.85 |
| 9 | 31.63 | 32.73 | 33.82 | 34.77 | 35.31 | 35.56 | 35.54 | 35.64 | 37.72 | 40.73 | 39.48 | 38.94 | 38.13 | 36.76 |
| 10 | 34.31 | 35.90 | 37.34 | 38.63 | 39.45 | 39.94 | 40.15 | 40.37 | 42.76 | 46.19 | 44.84 | 44.24 | 43.32 | 41.77 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 11.84 | 11.63 | 11.53 | 11.49 | 11.41 | 11.30 | 11.17 | 11.29 | 11.99 | 12.97 | 12.64 | 12.53 | 12.38 | 12.16 |
| 5 | 13.57 | 13.45 | 13.41 | 14.91 | 14.84 | 14.71 | 14.54 | 14.61 | 15.48 | 16.73 | 16.23 | 16.06 | 15.81 | 15.43 |
| 6 | 16.51 | 16.44 | 16.50 | 18.43 | 18.40 | 18.28 | 18.08 | 18.12 | 19.17 | 20.70 | 20.04 | 19.79 | 19.42 | 18.85 |
| 7 | 19.31 | 19.45 | 19.63 | 22.03 | 22.05 | 21.96 | 21.76 | 21.77 | 23.02 | 24.85 | 24.02 | 23.70 | 23.22 | 22.45 |
| 8 | 22.00 | 22.35 | 22.71 | 25.60 | 25.75 | 25.70 | 25.50 | 25.52 | 26.98 | 29.10 | 28.14 | 27.75 | 27.16 | 26.19 |
| 9 | 27.27 | 27.95 | 28.59 | 29.16 | 29.42 | 29.46 | 29.27 | 29.31 | 30.99 | 33.41 | 32.35 | 31.89 | 31.20 | 30.06 |
| 10 | 29.93 | 30.95 | 31.76 | 32.56 | 32.99 | 33.15 | 33.07 | 33.15 | 35.06 | 37.82 | 36.65 | 36.13 | 35.35 | 34.03 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 44.841 | 36.648 |
| SC2 | 0 | 8 | 30.921 | 25.516 |
| SC3 | -18 | 7 | 26.466 | 22.034 |
| SC4 | -25 | 6 | 19.682 | 16.498 |
| SC5 | -34 | 6 | 19.439 | 16.522 |
| A | 1725 mm |
|---|---|
| B | 1200 mm |
| C | 1150 mm |
| F | 1160 mm |
| G | 1740 mm |
| E | 1335 mm |
| D IN | 1 x Ø35 |
| D OUT | 1 x Ø54 |
| Length | 1725 mm |
|---|---|
| Width | 1740 mm |
| Height | 1150 mm |