EK-DI-363AC10-A08 C
46.53 kW
Defrost: None
Product code: EK-DI-263AE10-A13 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 36,754 m³/h |
|---|---|
| External surface | 158.7 m² |
| Inner volume | 66.6 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 415 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 5,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 68.0 dB(A) |
|---|---|
| Sound power | 91.0 dB(A) |
| Energy class | D |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø66,7 |
| EK-DI-263AE10-A13 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 19.94 | 19.42 | 19.07 | 18.85 | 18.58 | 18.30 | 18.02 | 17.95 | 18.95 | 20.38 | 19.77 | 19.54 | 19.22 | 18.74 |
| 5 | 23.55 | 23.13 | 22.91 | 25.30 | 25.03 | 24.69 | 24.32 | 24.17 | 25.52 | 27.45 | 26.57 | 26.24 | 25.79 | 25.10 |
| 6 | 29.06 | 28.95 | 28.93 | 32.15 | 31.93 | 31.61 | 31.20 | 31.01 | 32.74 | 35.21 | 34.03 | 33.59 | 32.97 | 32.02 |
| 7 | 34.39 | 34.67 | 34.95 | 39.13 | 39.12 | 38.89 | 38.51 | 38.29 | 40.43 | 43.52 | 42.06 | 41.51 | 40.69 | 39.44 |
| 8 | 39.45 | 40.22 | 40.77 | 45.99 | 46.26 | 46.23 | 45.96 | 45.81 | 48.41 | 52.17 | 50.48 | 49.82 | 48.86 | 47.32 |
| 9 | 48.75 | 50.10 | 51.41 | 52.62 | 53.38 | 53.67 | 53.56 | 53.51 | 56.60 | 61.09 | 59.23 | 58.49 | 57.39 | 55.61 |
| 10 | 53.31 | 55.25 | 57.04 | 58.66 | 59.71 | 60.34 | 60.64 | 60.95 | 64.64 | 70.02 | 68.14 | 67.32 | 66.11 | 64.11 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 17.40 | 16.91 | 16.61 | 16.44 | 16.25 | 16.04 | 15.84 | 15.83 | 16.75 | 18.06 | 17.56 | 17.38 | 17.12 | 16.73 |
| 5 | 20.39 | 20.00 | 19.77 | 21.83 | 21.61 | 21.35 | 21.08 | 21.00 | 22.20 | 23.92 | 23.21 | 22.95 | 22.58 | 22.03 |
| 6 | 25.24 | 24.97 | 24.80 | 27.52 | 27.35 | 27.08 | 26.76 | 26.64 | 28.14 | 30.30 | 29.34 | 28.99 | 28.48 | 27.71 |
| 7 | 29.93 | 29.90 | 29.96 | 33.42 | 33.34 | 33.09 | 32.77 | 32.61 | 34.45 | 37.11 | 35.91 | 35.46 | 34.80 | 33.78 |
| 8 | 34.46 | 34.75 | 35.08 | 39.35 | 39.43 | 39.30 | 39.01 | 38.85 | 41.05 | 44.25 | 42.83 | 42.28 | 41.44 | 40.14 |
| 9 | 43.09 | 43.86 | 44.47 | 45.16 | 45.48 | 45.50 | 45.31 | 45.21 | 47.80 | 51.56 | 49.96 | 49.31 | 48.36 | 46.82 |
| 10 | 47.54 | 48.63 | 49.83 | 50.96 | 51.54 | 51.76 | 51.70 | 51.69 | 54.69 | 59.04 | 57.30 | 56.57 | 55.50 | 53.72 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 68.139 | 57.298 |
| SC2 | 0 | 8 | 45.808 | 38.846 |
| SC3 | -18 | 7 | 39.159 | 33.407 |
| SC4 | -25 | 6 | 28.926 | 24.802 |
| SC5 | -34 | 6 | 29.081 | 25.209 |
| A | 3025 mm |
|---|---|
| B | 1000 mm |
| C | 1150 mm |
| F | 960 mm |
| G | 1540 mm |
| E1 | 1318 mm |
| E | 2635 mm |
| D IN | 1 x Ø35 |
| D OUT | 1 x Ø66,7 |
| Length | 3025 mm |
|---|---|
| Width | 1540 mm |
| Height | 1150 mm |