EK-DI-263AE10-A13 C
45.81 kW
Defrost: None
Product code: EK-DI-363AC10-A08 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 51,530 m³/h |
|---|---|
| External surface | 158.7 m² |
| Inner volume | 66.6 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 533 kg |
| Quantity | 3 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 5,700 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 73.0 dB(A) |
|---|---|
| Sound power | 97.0 dB(A) |
| Energy class | E |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø66,7 |
| EK-DI-363AC10-A08 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 20.08 | 19.53 | 19.15 | 18.91 | 18.63 | 18.34 | 18.06 | 17.94 | 18.93 | 20.37 | 19.74 | 19.51 | 19.19 | 18.71 |
| 5 | 23.80 | 23.35 | 23.10 | 25.49 | 25.20 | 24.85 | 24.48 | 24.29 | 25.63 | 27.56 | 26.67 | 26.34 | 25.88 | 25.15 |
| 6 | 29.45 | 29.31 | 29.25 | 32.50 | 32.26 | 31.93 | 31.53 | 31.29 | 33.02 | 35.51 | 34.32 | 33.88 | 33.24 | 32.28 |
| 7 | 34.93 | 35.17 | 35.44 | 39.66 | 39.64 | 39.41 | 39.03 | 38.77 | 40.94 | 44.06 | 42.58 | 42.02 | 41.22 | 39.98 |
| 8 | 40.14 | 40.73 | 41.42 | 46.70 | 46.98 | 46.95 | 46.70 | 46.53 | 49.17 | 53.00 | 51.31 | 50.66 | 49.70 | 48.19 |
| 9 | 49.58 | 50.91 | 52.19 | 53.40 | 54.18 | 54.60 | 54.54 | 54.48 | 57.64 | 62.22 | 60.37 | 59.64 | 58.56 | 56.80 |
| 10 | 54.27 | 56.18 | 57.96 | 59.59 | 60.65 | 61.31 | 61.66 | 61.98 | 65.74 | 71.25 | 69.61 | 68.81 | 67.62 | 65.65 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 17.92 | 17.40 | 17.07 | 16.87 | 16.66 | 16.45 | 16.24 | 16.16 | 17.07 | 18.39 | 17.87 | 17.68 | 17.40 | 17.00 |
| 5 | 21.09 | 20.68 | 20.42 | 22.53 | 22.29 | 22.02 | 21.72 | 21.59 | 22.80 | 24.55 | 23.80 | 23.53 | 23.14 | 22.55 |
| 6 | 26.18 | 25.89 | 25.71 | 28.52 | 28.34 | 28.07 | 27.72 | 27.55 | 29.09 | 31.31 | 30.32 | 29.95 | 29.42 | 28.62 |
| 7 | 31.11 | 31.08 | 31.15 | 34.75 | 34.67 | 34.43 | 34.08 | 33.91 | 35.82 | 38.57 | 37.34 | 36.88 | 36.21 | 35.12 |
| 8 | 35.86 | 36.19 | 36.54 | 41.01 | 41.12 | 41.01 | 40.71 | 40.53 | 42.82 | 46.16 | 44.68 | 44.14 | 43.33 | 42.02 |
| 9 | 44.88 | 45.57 | 46.38 | 47.13 | 47.50 | 47.58 | 47.40 | 47.28 | 50.00 | 53.96 | 52.39 | 51.72 | 50.77 | 49.23 |
| 10 | 49.26 | 50.54 | 51.81 | 53.02 | 53.82 | 54.23 | 54.19 | 54.18 | 57.35 | 61.96 | 60.24 | 59.52 | 58.45 | 56.70 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 69.605 | 60.238 |
| SC2 | 0 | 8 | 46.528 | 40.532 |
| SC3 | -18 | 7 | 39.678 | 34.737 |
| SC4 | -25 | 6 | 29.254 | 25.713 |
| SC5 | -34 | 6 | 29.464 | 26.151 |
| A | 4325 mm |
|---|---|
| B | 900 mm |
| C | 1150 mm |
| F | 860 mm |
| G | 1440 mm |
| E1 | 1318 mm |
| E2 | 1300 mm |
| E | 3935 mm |
| D IN | 1 x Ø35 |
| D OUT | 1 x Ø66,7 |
| Length | 4325 mm |
|---|---|
| Width | 1440 mm |
| Height | 1150 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.