EK-K-s-250AE10-B10 C
19.84 kW
Defrost: None
Product code: EK-K-b-250AE10-B22 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 15,198 m³/h |
|---|---|
| External surface | 78.1 m² |
| Inner volume | 34.7 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 211 kg |
| Quantity | 2 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,390 rpm |
| Power | 1,440 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 60.0 dB(A) |
|---|---|
| Sound power | 82.3 dB(A) |
| Energy class | D |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø54 |
| EK-K-b-250AE10-B22 C | None |
|---|---|
| EK-K-b-250AE10-B22 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 9.04 | 8.74 | 8.56 | 8.46 | 8.35 | 8.24 | 8.14 | 8.17 | 8.64 | 9.33 | 9.08 | 8.99 | 8.87 | 8.68 |
| 5 | 10.68 | 10.41 | 10.24 | 11.26 | 11.12 | 10.96 | 10.80 | 10.80 | 11.43 | 12.32 | 11.96 | 11.83 | 11.66 | 11.40 |
| 6 | 13.28 | 13.05 | 12.92 | 14.27 | 14.12 | 13.94 | 13.73 | 13.69 | 14.46 | 15.57 | 15.07 | 14.90 | 14.64 | 14.26 |
| 7 | 15.92 | 15.78 | 15.71 | 17.41 | 17.29 | 17.10 | 16.87 | 16.79 | 17.73 | 19.08 | 18.44 | 18.20 | 17.85 | 17.33 |
| 8 | 18.47 | 18.46 | 18.51 | 20.64 | 20.58 | 20.40 | 20.16 | 20.06 | 21.18 | 22.80 | 22.01 | 21.71 | 21.27 | 20.59 |
| 9 | 23.24 | 23.45 | 23.67 | 23.88 | 23.91 | 23.79 | 23.56 | 23.45 | 24.76 | 26.67 | 25.76 | 25.39 | 24.87 | 24.02 |
| 10 | 25.84 | 26.30 | 26.73 | 27.05 | 27.21 | 27.16 | 26.99 | 26.91 | 28.43 | 30.63 | 29.61 | 29.20 | 28.59 | 27.61 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 8.21 | 7.95 | 7.80 | 7.72 | 7.63 | 7.55 | 7.48 | 7.50 | 7.95 | 8.59 | 8.38 | 8.30 | 8.19 | 8.03 |
| 5 | 9.66 | 9.40 | 9.25 | 10.19 | 10.08 | 9.95 | 9.84 | 9.82 | 10.40 | 11.22 | 10.91 | 10.80 | 10.65 | 10.42 |
| 6 | 11.99 | 11.75 | 11.62 | 12.83 | 12.71 | 12.56 | 12.41 | 12.36 | 13.07 | 14.08 | 13.66 | 13.50 | 13.28 | 12.95 |
| 7 | 14.37 | 14.15 | 14.06 | 15.59 | 15.49 | 15.33 | 15.16 | 15.07 | 15.92 | 17.15 | 16.61 | 16.41 | 16.12 | 15.68 |
| 8 | 16.68 | 16.58 | 16.56 | 18.44 | 18.36 | 18.21 | 18.04 | 17.93 | 18.94 | 20.41 | 19.76 | 19.52 | 19.17 | 18.61 |
| 9 | 21.03 | 21.07 | 21.17 | 21.31 | 21.30 | 21.18 | 21.01 | 20.91 | 22.09 | 23.80 | 23.06 | 22.78 | 22.36 | 21.69 |
| 10 | 23.43 | 23.66 | 23.92 | 24.18 | 24.26 | 24.19 | 24.06 | 23.95 | 25.31 | 27.30 | 26.48 | 26.15 | 25.66 | 24.88 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 29.610 | 26.479 |
| SC2 | 0 | 8 | 20.058 | 17.934 |
| SC3 | -18 | 7 | 17.369 | 15.554 |
| SC4 | -25 | 6 | 12.919 | 11.615 |
| SC5 | -34 | 6 | 13.245 | 11.953 |
| A | 1260 mm |
|---|---|
| B | 900 mm |
| C | 1735 mm |
| F | 840 mm |
| G | 835 mm |
| E | 1850 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø54 |
| Length | 1260 mm |
|---|---|
| Width | 900 mm |
| Height | 1850 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.