EK-K-s-863BG10-B08 C
163.97 kW
Defrost: None
Product code: EK-K-b-863BG10-B29 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 110,241 m³/h |
|---|---|
| External surface | 586.0 m² |
| Inner volume | 243.2 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 1,152 kg |
| Quantity | 8 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 15,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 77.0 dB(A) |
|---|---|
| Sound power | 101.0 dB(A) |
| Energy class | D |
| Inlet | Ø54 |
|---|---|
| Outlet | Ø80 |
| EK-K-b-863BG10-B29 C | None |
|---|---|
| EK-K-b-863BG10-B29 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 72.08 | 70.30 | 69.11 | 68.32 | 67.32 | 66.21 | 65.04 | 65.76 | 69.53 | 74.86 | 72.66 | 71.84 | 70.70 | 68.99 |
| 5 | 84.97 | 83.57 | 82.85 | 91.51 | 90.46 | 89.07 | 87.45 | 87.85 | 93.00 | 100.17 | 97.01 | 95.92 | 94.40 | 92.17 |
| 6 | 104.70 | 104.43 | 104.41 | 116.06 | 115.16 | 113.75 | 111.86 | 111.99 | 118.38 | 127.39 | 122.92 | 121.33 | 119.07 | 115.69 |
| 7 | 123.74 | 124.88 | 125.98 | 141.04 | 140.84 | 139.66 | 137.71 | 137.56 | 145.33 | 156.43 | 150.73 | 148.59 | 145.49 | 140.61 |
| 8 | 141.86 | 144.73 | 146.80 | 165.55 | 166.33 | 165.76 | 164.08 | 163.97 | 173.24 | 186.65 | 179.82 | 177.18 | 173.29 | 167.07 |
| 9 | 175.19 | 180.22 | 184.98 | 189.28 | 191.78 | 192.23 | 190.99 | 191.04 | 201.94 | 217.74 | 210.20 | 207.11 | 202.54 | 195.06 |
| 10 | 191.54 | 198.66 | 205.17 | 210.97 | 214.32 | 216.03 | 216.22 | 217.51 | 230.46 | 249.25 | 241.09 | 237.61 | 232.42 | 223.81 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 71.88 | 70.21 | 69.06 | 68.28 | 67.26 | 66.03 | 64.79 | 65.75 | 69.52 | 74.86 | 72.65 | 71.84 | 70.69 | 68.98 |
| 5 | 84.83 | 83.48 | 82.79 | 91.43 | 90.34 | 88.77 | 87.00 | 87.82 | 92.97 | 100.14 | 96.99 | 95.90 | 94.39 | 92.16 |
| 6 | 104.55 | 104.33 | 104.34 | 115.96 | 114.98 | 113.31 | 111.20 | 111.91 | 118.38 | 127.39 | 122.87 | 121.27 | 119.02 | 115.69 |
| 7 | 123.58 | 124.77 | 125.90 | 140.93 | 140.62 | 139.09 | 136.83 | 137.04 | 144.81 | 155.89 | 149.97 | 147.76 | 144.57 | 139.54 |
| 8 | 141.68 | 144.61 | 146.72 | 165.43 | 166.08 | 165.08 | 163.02 | 163.15 | 172.36 | 185.68 | 178.48 | 175.70 | 171.58 | 164.98 |
| 9 | 175.01 | 180.11 | 184.90 | 189.18 | 191.55 | 191.45 | 189.74 | 189.95 | 200.72 | 216.33 | 208.33 | 205.02 | 200.12 | 192.08 |
| 10 | 191.35 | 198.54 | 205.10 | 210.87 | 214.03 | 215.23 | 214.96 | 216.36 | 229.14 | 247.42 | 238.71 | 234.93 | 229.30 | 219.93 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 241.093 | 238.710 |
| SC2 | 0 | 8 | 163.966 | 163.152 |
| SC3 | -18 | 7 | 141.091 | 140.948 |
| SC4 | -25 | 6 | 104.414 | 104.339 |
| SC5 | -34 | 6 | 104.795 | 104.649 |
| A | 4460 mm |
|---|---|
| B | 1150 mm |
| C | 1935 mm |
| F | 1090 mm |
| G | 4035 mm |
| E | 2050 mm |
| G1 | 1035 mm |
| G2 | 1000 mm |
| D IN | 2 x Ø54 |
| D OUT | 2 x Ø80 |
| Length | 4460 mm |
|---|---|
| Width | 1150 mm |
| Height | 2050 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.