EK-K-b-263BE10-B29 C
33.48 kW
Defrost: None
Product code: EK-K-s-263BE10-B08 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 29,740 m³/h |
|---|---|
| External surface | 109.9 m² |
| Inner volume | 46.0 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 318 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 3,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 72.0 dB(A) |
|---|---|
| Sound power | 95.0 dB(A) |
| Energy class | E |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø42 |
| EK-K-s-263BE10-B08 C | None |
|---|---|
| EK-K-s-263BE10-B08 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 14.72 | 14.19 | 13.84 | 13.61 | 13.37 | 13.15 | 12.93 | 12.96 | 13.68 | 14.74 | 14.32 | 14.17 | 13.96 | 13.64 |
| 5 | 17.62 | 17.13 | 16.80 | 18.40 | 18.09 | 17.76 | 17.42 | 17.42 | 18.42 | 19.82 | 19.20 | 18.98 | 18.65 | 18.17 |
| 6 | 22.18 | 21.72 | 21.45 | 23.62 | 23.29 | 22.89 | 22.44 | 22.38 | 23.63 | 25.40 | 24.52 | 24.21 | 23.78 | 23.13 |
| 7 | 26.66 | 26.44 | 26.31 | 29.13 | 28.82 | 28.41 | 27.89 | 27.78 | 29.32 | 31.49 | 30.33 | 29.91 | 29.31 | 28.41 |
| 8 | 31.02 | 31.08 | 31.18 | 34.75 | 34.58 | 34.20 | 33.65 | 33.49 | 35.34 | 37.97 | 36.53 | 35.99 | 35.21 | 34.00 |
| 9 | 39.11 | 39.58 | 39.92 | 40.31 | 40.34 | 40.07 | 39.58 | 39.41 | 41.59 | 44.74 | 43.04 | 42.38 | 41.43 | 39.91 |
| 10 | 43.22 | 44.13 | 45.03 | 45.87 | 46.15 | 46.05 | 45.64 | 45.49 | 48.03 | 51.71 | 49.84 | 49.08 | 47.98 | 46.19 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 12.93 | 12.48 | 12.20 | 12.03 | 11.87 | 11.70 | 11.54 | 11.66 | 12.33 | 13.31 | 12.97 | 12.84 | 12.67 | 12.42 |
| 5 | 15.36 | 14.92 | 14.63 | 16.06 | 15.82 | 15.57 | 15.32 | 15.39 | 16.30 | 17.58 | 17.08 | 16.91 | 16.68 | 16.32 |
| 6 | 19.22 | 18.80 | 18.54 | 20.41 | 20.15 | 19.84 | 19.49 | 19.50 | 20.61 | 22.20 | 21.48 | 21.23 | 20.87 | 20.36 |
| 7 | 23.15 | 22.82 | 22.60 | 25.00 | 24.75 | 24.41 | 23.99 | 23.93 | 25.27 | 27.19 | 26.23 | 25.88 | 25.39 | 24.64 |
| 8 | 26.98 | 26.82 | 26.77 | 29.74 | 29.53 | 29.19 | 28.74 | 28.62 | 30.21 | 32.50 | 31.30 | 30.85 | 30.21 | 29.21 |
| 9 | 34.11 | 34.20 | 34.36 | 34.53 | 34.44 | 34.15 | 33.67 | 33.52 | 35.38 | 38.07 | 36.65 | 36.09 | 35.29 | 34.02 |
| 10 | 38.08 | 38.51 | 38.93 | 39.33 | 39.33 | 39.13 | 38.71 | 38.54 | 40.69 | 43.77 | 42.18 | 41.54 | 40.59 | 39.07 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 49.838 | 42.184 |
| SC2 | 0 | 8 | 33.488 | 28.623 |
| SC3 | -18 | 7 | 29.035 | 24.912 |
| SC4 | -25 | 6 | 21.453 | 18.540 |
| SC5 | -34 | 6 | 22.115 | 19.148 |
| A | 1460 mm |
|---|---|
| B | 1050 mm |
| C | 1935 mm |
| F | 840 mm |
| G | 1035 mm |
| E | 2050 mm |
| D IN | 2 x Ø19 |
| D OUT | 2 x Ø42 |
| Length | 1460 mm |
|---|---|
| Width | 1050 mm |
| Height | 2050 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.