EK-K-b-263BG10-B29 C
41.13 kW
Defrost: None
Product code: EK-K-s-263BG10-B08 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 27,612 m³/h |
|---|---|
| External surface | 146.5 m² |
| Inner volume | 62.4 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 358 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 3,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 72.0 dB(A) |
|---|---|
| Sound power | 95.0 dB(A) |
| Energy class | D |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø54 |
| EK-K-s-263BG10-B08 C | None |
|---|---|
| EK-K-s-263BG10-B08 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 18.55 | 17.91 | 17.51 | 17.27 | 17.01 | 16.74 | 16.48 | 16.70 | 17.64 | 19.03 | 18.52 | 18.34 | 18.08 | 17.70 |
| 5 | 22.02 | 21.42 | 21.04 | 23.09 | 22.74 | 22.36 | 21.95 | 22.07 | 23.37 | 25.19 | 24.45 | 24.20 | 23.85 | 23.35 |
| 6 | 27.48 | 26.97 | 26.65 | 29.37 | 28.99 | 28.53 | 27.99 | 28.00 | 29.61 | 31.86 | 30.78 | 30.40 | 29.88 | 29.11 |
| 7 | 33.02 | 32.67 | 32.49 | 35.94 | 35.60 | 35.11 | 34.48 | 34.40 | 36.32 | 39.05 | 37.62 | 37.10 | 36.36 | 35.23 |
| 8 | 38.36 | 38.31 | 38.36 | 42.70 | 42.47 | 41.97 | 41.30 | 41.14 | 43.41 | 46.69 | 44.90 | 44.23 | 43.26 | 41.74 |
| 9 | 48.34 | 48.72 | 49.12 | 49.49 | 49.43 | 49.04 | 48.37 | 48.15 | 50.80 | 54.65 | 52.56 | 51.71 | 50.52 | 48.60 |
| 10 | 53.80 | 54.70 | 55.38 | 56.12 | 56.28 | 56.06 | 55.47 | 55.30 | 58.36 | 62.79 | 60.46 | 59.51 | 58.11 | 55.83 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 16.05 | 15.52 | 15.21 | 15.04 | 14.86 | 14.68 | 14.49 | 14.71 | 15.63 | 16.89 | 16.49 | 16.34 | 16.13 | 15.82 |
| 5 | 18.90 | 18.37 | 18.05 | 19.85 | 19.60 | 19.32 | 19.01 | 19.17 | 20.32 | 21.94 | 21.34 | 21.13 | 20.85 | 20.44 |
| 6 | 23.50 | 22.98 | 22.68 | 25.00 | 24.71 | 24.36 | 23.95 | 24.01 | 25.41 | 27.39 | 26.51 | 26.20 | 25.77 | 25.13 |
| 7 | 28.19 | 27.70 | 27.47 | 30.39 | 30.11 | 29.71 | 29.22 | 29.19 | 30.84 | 33.21 | 32.04 | 31.62 | 31.01 | 30.07 |
| 8 | 32.79 | 32.50 | 32.39 | 35.94 | 35.71 | 35.30 | 34.75 | 34.64 | 36.57 | 39.37 | 37.91 | 37.35 | 36.55 | 35.29 |
| 9 | 41.42 | 41.35 | 41.45 | 41.60 | 41.45 | 41.05 | 40.47 | 40.30 | 42.53 | 45.76 | 44.05 | 43.37 | 42.38 | not rated |
| 10 | 46.23 | 46.52 | 46.88 | 47.25 | 47.21 | 46.89 | 46.31 | 46.13 | 48.68 | 52.36 | 50.42 | 49.62 | 48.44 | not rated |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 60.460 | 50.424 |
| SC2 | 0 | 8 | 41.137 | 34.638 |
| SC3 | -18 | 7 | 35.826 | 30.297 |
| SC4 | -25 | 6 | 26.648 | 22.678 |
| SC5 | -34 | 6 | 27.400 | 23.409 |
| A | 1460 mm |
|---|---|
| B | 1150 mm |
| C | 1935 mm |
| F | 940 mm |
| G | 1035 mm |
| E | 2050 mm |
| D IN | 2 x Ø22 |
| D OUT | 2 x Ø54 |
| Length | 1460 mm |
|---|---|
| Width | 1150 mm |
| Height | 2050 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.