EK-SR-180AG7-A05 C
31.37 kW
Defrost: None
Product code: EK-SR-180BE7-A05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 24,143 m³/h |
|---|---|
| External surface | 131.5 m² |
| Inner volume | 38.5 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 500 kg |
| Quantity | 1 |
|---|---|
| Diameter | 800 mm |
| Speed | 1,310 rpm |
| Power | 3,900 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 69.0 dB(A) |
|---|---|
| Sound power | 92.7 dB(A) |
| Energy class | E |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø42 |
| EK-SR-180BE7-A05 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 12.98 | 12.87 | 12.85 | 12.84 | 12.75 | 12.62 | 12.46 | 12.52 | 13.22 | 14.24 | 13.83 | 13.68 | 13.47 | 13.14 |
| 5 | 14.98 | 15.17 | 15.32 | 17.16 | 17.13 | 16.99 | 16.80 | 16.84 | 17.82 | 19.21 | 18.64 | 18.43 | 18.14 | 17.69 |
| 6 | 18.12 | 18.65 | 19.09 | 21.50 | 21.66 | 21.63 | 21.48 | 21.52 | 22.78 | 24.55 | 23.80 | 23.52 | 23.11 | 22.50 |
| 7 | 20.90 | 21.76 | 22.53 | 25.79 | 26.27 | 26.42 | 26.36 | 26.45 | 28.01 | 30.24 | 29.33 | 28.98 | 28.46 | 27.63 |
| 8 | 23.31 | 24.53 | ≈ 25.63 | ≈ 29.54 | 30.24 | 30.65 | 30.85 | 31.14 | 33.05 | 35.85 | 35.02 | 34.69 | 34.09 | 33.10 |
| 9 | 28.37 | 30.17 | 31.79 | 33.20 | 34.16 | 34.76 | 35.09 | 35.45 | 37.65 | 40.86 | 39.94 | 39.56 | 38.99 | 38.04 |
| 10 | 30.62 | 32.90 | 34.96 | 36.76 | 38.02 | 38.85 | 39.33 | 39.79 | 42.27 | 45.91 | 44.92 | 44.49 | 43.85 | 42.77 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 11.52 | 11.42 | 11.37 | 11.35 | 11.28 | 11.17 | 11.05 | 11.14 | 11.80 | 12.73 | 12.40 | 12.28 | 12.10 | 11.84 |
| 5 | 13.36 | 13.41 | 13.47 | 15.01 | 14.98 | 14.87 | 14.71 | 14.77 | 15.64 | 16.88 | 16.40 | 16.24 | 16.00 | 15.64 |
| 6 | 16.21 | 16.50 | 16.76 | 18.86 | 18.91 | 18.84 | 18.66 | 18.71 | 19.80 | 21.36 | 20.71 | 20.47 | 20.12 | 19.60 |
| 7 | 18.90 | 19.50 | 19.93 | 22.62 | 22.85 | 22.89 | 22.78 | 22.83 | 24.17 | 26.09 | 25.28 | 24.98 | 24.53 | 23.82 |
| 8 | 21.25 | 22.13 | 22.93 | 26.27 | 26.77 | 27.02 | 27.00 | 27.10 | 28.70 | 31.02 | 30.10 | 29.74 | 29.20 | 28.33 |
| 9 | 25.97 | 27.30 | 28.51 | 29.56 | 30.26 | 30.68 | 30.88 | 31.14 | 33.05 | 35.85 | 35.01 | 34.64 | 34.02 | 32.99 |
| 10 | 28.14 | 29.86 | 31.42 | 32.78 | 33.71 | 34.27 | 34.58 | 34.93 | 37.08 | 40.23 | 39.31 | 38.92 | 38.34 | 37.35 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 44.916 | 39.313 |
| SC2 | 0 | 8 | 31.136 | 27.102 |
| SC3 | -18 | 7 | 26.014 | 22.736 |
| SC4 | -25 | 6 | 19.091 | 16.757 |
| SC5 | -34 | 6 | 18.260 | 16.298 |
| A | 1760 mm |
|---|---|
| B | 1360 mm |
| C | 2790 mm |
| F | 1310 mm |
| G | 1770 mm |
| E | 1365 mm |
| H | 1393 mm |
| I | 1790 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø42 |
| Length | 1760 mm |
|---|---|
| Width | 1393 mm |
| Height | 2790 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.