EK-SR-491CC10-A04 C
93.20 kW
Defrost: None
Product code: EK-SR-280CE4-A05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 49,350 m³/h |
|---|---|
| External surface | 488.7 m² |
| Inner volume | 97.8 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 863 kg |
| Quantity | 2 |
|---|---|
| Diameter | 800 mm |
| Speed | 1,310 rpm |
| Power | 7,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 72.0 dB(A) |
|---|---|
| Sound power | 95.9 dB(A) |
| Energy class | D |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø54 |
| EK-SR-280CE4-A05 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 40.62 | 40.23 | 40.18 | 40.24 | 40.11 | 39.86 | 39.55 | 39.81 | 42.22 | 45.67 | 44.61 | 44.23 | 43.65 | 42.78 |
| 5 | 46.55 | 46.85 | 47.19 | 52.80 | 52.78 | 52.48 | 52.05 | 52.24 | 55.34 | 59.79 | 58.20 | 57.62 | 56.81 | 55.60 |
| 6 | 56.19 | 57.35 | 58.13 | 65.58 | 65.94 | 65.86 | 65.45 | 65.60 | 69.46 | 75.02 | 72.84 | 72.04 | 70.89 | 69.11 |
| 7 | 64.71 | 66.75 | 68.65 | 78.19 | 79.38 | 79.74 | 79.50 | 79.68 | 84.35 | 91.15 | 88.48 | 87.45 | 85.94 | 83.55 |
| 8 | 72.37 | 75.39 | 78.11 | 89.48 | 91.19 | 92.16 | 92.56 | 93.22 | 98.89 | 107.22 | 104.66 | 103.58 | 101.75 | 98.79 |
| 9 | 88.33 | 92.90 | 97.00 | 100.59 | 102.95 | 104.33 | 105.00 | 105.83 | 112.29 | 121.74 | 118.88 | 117.69 | 115.91 | 112.96 |
| 10 | 95.62 | 101.53 | 106.84 | 111.45 | 114.56 | 116.49 | 117.50 | 118.56 | 125.83 | 136.44 | 133.31 | 131.97 | 129.94 | 126.54 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 35.40 | 35.04 | 34.92 | 34.96 | 34.88 | 34.71 | 34.49 | 34.83 | 36.99 | 40.06 | 39.21 | 38.90 | 38.48 | 37.86 |
| 5 | 40.63 | 40.57 | 40.68 | 45.35 | 45.33 | 45.13 | 44.80 | 45.05 | 47.76 | 51.67 | 50.36 | 49.89 | 49.22 | 48.23 |
| 6 | 49.13 | 49.62 | 50.13 | 56.27 | 56.41 | 56.25 | 55.83 | 56.00 | 59.30 | 64.10 | 62.30 | 61.63 | 60.64 | 59.16 |
| 7 | 57.28 | 58.50 | 59.39 | 67.11 | 67.61 | 67.64 | 67.32 | 67.45 | 71.40 | 77.16 | 74.89 | 74.02 | 72.74 | 70.71 |
| 8 | 64.52 | 66.48 | 68.33 | 77.82 | 79.00 | 79.34 | 79.14 | 79.33 | 83.98 | 90.77 | 88.12 | 87.06 | 85.49 | 82.95 |
| 9 | 79.04 | 82.15 | 84.99 | 87.54 | 89.16 | 90.05 | 90.40 | 91.02 | 96.52 | 104.58 | 101.74 | 100.50 | 98.65 | 95.63 |
| 10 | 85.91 | 90.05 | 93.81 | 97.11 | 99.23 | 100.50 | 101.07 | 101.82 | 107.99 | 117.00 | 114.21 | 113.00 | 111.19 | 108.16 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 133.309 | 114.208 |
| SC2 | 0 | 8 | 93.216 | 79.333 |
| SC3 | -18 | 7 | 78.741 | 67.371 |
| SC4 | -25 | 6 | 58.133 | 50.128 |
| SC5 | -34 | 6 | 56.526 | 49.303 |
| A | 3060 mm |
|---|---|
| B | 1360 mm |
| C | 3090 mm |
| F | 1310 mm |
| G | 2070 mm |
| E | 2665 mm |
| H | 1393 mm |
| I | 3090 mm |
| D IN | 2 x Ø28 |
| D OUT | 2 x Ø54 |
| Length | 3060 mm |
|---|---|
| Width | 1393 mm |
| Height | 3090 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.