EK-SR-280CE10-A05 C
66.10 kW
Defrost: None
Product code: EK-SR-291DC7-A03 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 68,437 m³/h |
|---|---|
| External surface | 263.6 m² |
| Inner volume | 82.9 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 836 kg |
| Quantity | 2 |
|---|---|
| Diameter | 910 mm |
| Speed | 1,210 rpm |
| Power | 10,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 68.0 dB(A) |
|---|---|
| Sound power | 92.7 dB(A) |
| Energy class | E |
| Inlet | Ø42 |
|---|---|
| Outlet | Ø66,7 |
| EK-SR-291DC7-A03 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 27.71 | 27.17 | 26.82 | 26.61 | 26.32 | 26.00 | 25.69 | 25.64 | 27.08 | 29.19 | 28.37 | 28.08 | 27.66 | 27.03 |
| 5 | 32.67 | 32.42 | 32.28 | 35.73 | 35.46 | 35.08 | 34.64 | 34.53 | 36.50 | 39.31 | 38.14 | 37.70 | 37.08 | 36.13 |
| 6 | 40.21 | 40.47 | 40.72 | 45.49 | 45.39 | 45.05 | 44.54 | 44.38 | 46.90 | 50.50 | 48.92 | 48.34 | 47.51 | 46.23 |
| 7 | 47.42 | 48.18 | 49.01 | 55.24 | 55.51 | 55.40 | 55.03 | 54.89 | 58.04 | 62.54 | 60.57 | 59.84 | 58.77 | 57.11 |
| 8 | 53.56 | 55.16 | 56.66 | 64.48 | 65.44 | 65.97 | 65.90 | 65.88 | 69.71 | 75.22 | 72.98 | 72.11 | 70.83 | 68.79 |
| 9 | 65.84 | 68.43 | 70.79 | 72.91 | 74.28 | 75.10 | 75.51 | 75.99 | 80.62 | 87.39 | 85.41 | 84.62 | 83.40 | 81.05 |
| 10 | 71.75 | 75.26 | 78.42 | 81.21 | 83.08 | 84.25 | 84.90 | 85.53 | 90.78 | 98.46 | 96.28 | 95.40 | 94.08 | 91.90 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 23.88 | 23.35 | 23.04 | 22.89 | 22.70 | 22.49 | 22.28 | 22.36 | 23.65 | 25.55 | 24.91 | 24.68 | 24.35 | 23.86 |
| 5 | 28.02 | 27.56 | 27.37 | 30.32 | 30.11 | 29.84 | 29.52 | 29.54 | 31.26 | 33.74 | 32.83 | 32.50 | 32.04 | 31.35 |
| 6 | 34.51 | 34.39 | 34.39 | 38.28 | 38.11 | 37.83 | 37.46 | 37.40 | 39.56 | 42.67 | 41.42 | 40.96 | 40.32 | 39.34 |
| 7 | 40.84 | 41.15 | 41.49 | 46.48 | 46.51 | 46.30 | 45.93 | 45.83 | 48.46 | 52.26 | 50.68 | 50.09 | 49.21 | 47.89 |
| 8 | 46.90 | 47.77 | 48.41 | 54.60 | 54.94 | 54.93 | 54.66 | 54.60 | 57.76 | 62.32 | 60.43 | 59.71 | 58.66 | 56.99 |
| 9 | 58.03 | 59.61 | 61.13 | 62.56 | 63.47 | 63.74 | 63.63 | 63.66 | 67.38 | 72.78 | 70.66 | 69.82 | 68.59 | 66.60 |
| 10 | 63.50 | 65.75 | 67.84 | 69.75 | 70.99 | 71.74 | 72.10 | 72.54 | 76.96 | 83.43 | 81.14 | 80.20 | 78.81 | 76.54 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 96.280 | 81.143 |
| SC2 | 0 | 8 | 65.883 | 54.603 |
| SC3 | -18 | 7 | 55.404 | 46.527 |
| SC4 | -25 | 6 | 40.720 | 34.387 |
| SC5 | -34 | 6 | 40.328 | 34.529 |
| A | 3060 mm |
|---|---|
| B | 1360 mm |
| C | 3390 mm |
| F | 1310 mm |
| G | 2370 mm |
| E | 2665 mm |
| H | 1393 mm |
| I | 3090 mm |
| D IN | 1 x Ø42 |
| D OUT | 1 x Ø66,7 |
| Length | 3060 mm |
|---|---|
| Width | 1393 mm |
| Height | 3390 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.