EK-SR-480BG10-A05 C
140.34 kW
Defrost: None
Product code: EK-SR-380CE4-A05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 74,025 m³/h |
|---|---|
| External surface | 733.0 m² |
| Inner volume | 146.8 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 1,154 kg |
| Quantity | 3 |
|---|---|
| Diameter | 800 mm |
| Speed | 1,310 rpm |
| Power | 11,700 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 73.0 dB(A) |
|---|---|
| Sound power | 97.9 dB(A) |
| Energy class | D |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø66,7 |
| EK-SR-380CE4-A05 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 61.08 | 60.45 | 60.33 | 60.40 | 60.18 | 59.80 | 59.32 | 59.71 | 63.32 | 68.49 | 66.90 | 66.32 | 65.46 | 64.15 |
| 5 | 70.07 | 70.44 | 70.89 | 79.27 | 79.21 | 78.74 | 78.08 | 78.36 | 83.00 | 89.67 | 87.28 | 86.42 | 85.20 | 83.37 |
| 6 | 84.66 | 86.29 | 87.38 | 98.50 | 99.00 | 98.84 | 98.20 | 98.41 | 104.19 | 112.52 | 109.25 | 108.05 | 106.31 | 103.64 |
| 7 | 97.52 | 100.46 | 103.21 | 117.47 | 119.18 | 119.69 | 119.29 | 119.54 | 126.55 | 136.73 | 132.72 | 131.17 | 128.90 | 125.30 |
| 8 | 109.14 | 113.52 | 117.49 | 134.47 | 136.95 | 138.35 | 138.90 | 139.86 | 148.37 | 160.86 | 157.00 | 155.37 | 152.62 | 148.17 |
| 9 | 133.29 | 139.96 | 145.97 | 151.22 | 154.66 | 156.65 | 157.60 | 158.81 | 168.49 | 182.65 | 178.34 | 176.55 | 173.87 | 169.43 |
| 10 | 144.37 | 153.05 | 160.84 | 167.60 | 172.14 | 174.94 | 176.39 | 177.92 | 188.81 | 204.71 | 199.99 | 197.96 | 194.92 | 189.80 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 53.21 | 52.63 | 52.42 | 52.47 | 52.33 | 52.07 | 51.73 | 52.24 | 55.47 | 60.09 | 58.79 | 58.34 | 57.71 | 56.78 |
| 5 | 61.11 | 60.97 | 61.08 | 68.07 | 68.02 | 67.70 | 67.20 | 67.57 | 71.63 | 77.49 | 75.52 | 74.81 | 73.82 | 72.33 |
| 6 | 73.95 | 74.59 | 75.31 | 84.48 | 84.66 | 84.39 | 83.75 | 83.99 | 88.95 | 96.13 | 93.44 | 92.44 | 90.95 | 88.72 |
| 7 | 86.28 | 87.99 | 89.26 | 100.79 | 101.49 | 101.51 | 101.00 | 101.19 | 107.11 | 115.74 | 112.32 | 111.01 | 109.09 | 106.04 |
| 8 | 97.21 | 100.03 | 102.72 | 116.89 | 118.61 | 119.08 | 118.76 | 119.02 | 125.99 | 136.16 | 132.18 | 130.58 | 128.23 | 124.40 |
| 9 | 119.17 | 123.67 | 127.82 | 131.54 | 133.90 | 135.17 | 135.66 | 136.56 | 144.81 | 156.89 | 152.61 | 150.74 | 147.97 | 143.42 |
| 10 | 129.59 | 135.63 | 141.12 | 145.96 | 149.04 | 150.89 | 151.69 | 152.78 | 162.03 | 175.53 | 171.32 | 169.51 | 166.78 | 162.23 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 199.989 | 171.322 |
| SC2 | 0 | 8 | 139.862 | 119.022 |
| SC3 | -18 | 7 | 118.267 | 101.164 |
| SC4 | -25 | 6 | 87.380 | 75.305 |
| SC5 | -34 | 6 | 85.129 | 74.191 |
| A | 4360 mm |
|---|---|
| B | 1360 mm |
| C | 3090 mm |
| F | 1310 mm |
| G | 2070 mm |
| E | 3965 mm |
| H | 1393 mm |
| I | 4390 mm |
| D IN | 2 x Ø35 |
| D OUT | 2 x Ø66,7 |
| Length | 4360 mm |
|---|---|
| Width | 1393 mm |
| Height | 3090 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.