EK-SR-391CC7-A04 C
84.89 kW
Defrost: None
Product code: EK-SR-480BC7-A05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 102,445 m³/h |
|---|---|
| External surface | 351.5 m² |
| Inner volume | 105.1 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 1,125 kg |
| Quantity | 4 |
|---|---|
| Diameter | 800 mm |
| Speed | 1,310 rpm |
| Power | 15,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 74.0 dB(A) |
|---|---|
| Sound power | 99.0 dB(A) |
| Energy class | E |
| Inlet | Ø42 |
|---|---|
| Outlet | Ø66,7 |
| EK-SR-480BC7-A05 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 35.07 | 35.16 | 35.22 | 35.21 | 35.02 | 34.68 | 34.26 | 34.16 | 36.05 | 38.80 | 37.61 | 37.17 | 36.54 | 35.60 |
| 5 | 40.34 | 41.24 | 41.98 | 47.26 | 47.39 | 47.18 | 46.75 | 46.59 | 49.27 | 53.08 | 51.47 | 50.86 | 49.97 | 48.59 |
| 6 | 48.52 | 50.17 | 51.84 | 59.12 | 59.91 | 60.15 | 60.00 | 60.09 | 63.61 | 68.63 | 66.60 | 65.83 | 64.71 | 62.95 |
| 7 | 55.08 | 57.86 | ≈ 60.37 | ≈ 69.51 | 71.13 | 72.14 | 72.69 | 73.35 | 77.90 | 84.49 | 82.70 | 81.80 | 80.46 | 78.32 |
| 8 | 61.22 | 65.06 | ≈ 68.52 | ≈ 79.49 | 81.82 | 83.33 | 84.24 | 85.13 | 90.45 | 98.20 | 96.20 | 95.39 | 94.17 | 92.15 |
| 9 | 74.24 | 79.77 | 84.80 | 89.20 | 92.34 | 94.47 | 95.81 | 97.01 | 103.13 | 112.08 | 109.91 | 109.01 | 107.64 | 105.36 |
| 10 | ≈ 79.88 | 86.72 | 93.00 | 98.55 | 102.63 | 105.49 | 107.35 | 108.92 | 115.88 | 126.06 | 123.78 | 122.80 | 121.31 | 118.76 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 31.85 | 31.63 | 31.61 | 31.63 | 31.46 | 31.17 | 30.83 | 30.89 | 32.63 | 35.17 | 34.17 | 33.80 | 33.28 | 32.49 |
| 5 | 36.71 | 37.20 | 37.62 | 42.19 | 42.20 | 41.93 | 41.54 | 41.60 | 44.02 | 47.47 | 46.10 | 45.59 | 44.88 | 43.76 |
| 6 | 44.35 | 45.67 | 46.57 | 52.78 | 53.25 | 53.30 | 53.04 | 53.15 | 56.26 | 60.71 | 58.91 | 58.25 | 57.29 | 55.81 |
| 7 | 51.03 | 53.13 | 55.04 | 63.06 | 64.29 | 64.98 | 65.00 | 65.26 | 69.14 | 74.72 | 72.64 | 71.82 | 70.63 | 68.72 |
| 8 | 56.93 | 59.91 | ≈ 62.61 | ≈ 72.20 | 73.97 | 75.09 | 75.71 | 76.45 | 81.20 | 88.12 | 86.24 | 85.48 | 84.36 | 82.34 |
| 9 | 69.29 | 73.67 | 77.64 | 81.12 | 83.55 | 85.13 | 86.08 | 87.03 | 92.47 | 100.43 | 98.36 | 97.50 | 96.21 | 94.07 |
| 10 | 74.80 | 80.34 | 85.38 | 89.81 | 92.97 | 95.12 | 96.44 | 97.67 | 103.83 | 112.86 | 110.62 | 109.67 | 108.24 | 105.82 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 123.776 | 110.617 |
| SC2 | 0 | 8 | 85.131 | 76.449 |
| SC3 | -18 | 7 | 70.247 | 63.622 |
| SC4 | -25 | 6 | 51.840 | 46.571 |
| SC5 | -34 | 6 | 48.695 | 44.701 |
| A | 5660 mm |
|---|---|
| B | 1360 mm |
| C | 2790 mm |
| F | 1310 mm |
| G | 1770 mm |
| E | 5265 mm |
| H | 1393 mm |
| I | 5690 mm |
| D IN | 1 x Ø42 |
| D OUT | 1 x Ø66,7 |
| Length | 5660 mm |
|---|---|
| Width | 1393 mm |
| Height | 2790 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.