Blast freezer EK-SR-480BG4-A05 C

Blast freezer EK-SR-480BG4-A05 C
Illustrative photo

Producer: Karyer · Line: EK-SR (Blast Freezers)

Product code: EK-SR-480BG4-A05 C

Cooling capacity i
181.89 kW
Air flow
86,285 m³/h
Fin spacing
4.6 mm
Fans
4 × ⌀800 mm

Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %

Data

Evaporator
Air flow 86,285 m³/h
External surface 1,042.5 m²
Inner volume 204.4 dm³
Fin spacing 4.6 mm
Fin materialAluminium
Net weight 1,406 kg
Fans
Quantity 4
Diameter 800 mm
Speed 1,310 rpm
Power 15,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 72.0 dB(A)
Sound power 97.3 dB(A)
Energy class E
Connections
Inlet Ø35
Outlet Ø66,7
Defrost
EK-SR-480BG4-A05 C None

Performance

TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.

R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)

High speed (Δ)
181.887 kW
Low speed (Y)
154.970 kW

Capacity matrix [kW]

R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.

≈ 1.23 estimate — vendor data irregular here

High speed (Δ)

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 77.81 79.34 80.65 81.75 82.06 81.72 81.08 82.35 87.52 94.77 92.57 91.80 90.73 89.12
5 86.94 90.22 92.49 105.30 106.57 106.83 106.28 107.48 114.06 123.44 120.03 118.82 117.09 114.49
6 101.61 106.68 111.26 ≈ 128.05 130.87 132.42 132.65 133.97 142.09 153.84 149.48 147.78 145.27 141.28
7 114.53 121.69 ≈ 128.15 ≈ 148.60 152.75 155.17 156.20 158.16 167.98 182.37 177.98 176.20 173.49 168.96
8 126.30 135.69 ≈ 144.25 ≈ 168.57 174.31 177.85 179.52 181.89 193.20 209.77 204.76 202.61 199.30 193.71
9 ≈ 152.13 165.19 177.26 187.84 195.39 200.21 202.80 205.74 218.59 237.36 231.89 229.38 225.54 218.92
10 162.70 178.47 193.21 206.30 215.83 222.27 225.96 229.60 244.06 265.10 259.25 256.45 252.10 244.51

Low speed (Y)

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 67.96 68.58 69.08 69.81 70.00 69.79 69.28 70.35 74.78 81.05 79.24 78.61 77.74 76.49
5 76.19 78.00 79.62 90.01 90.64 90.59 89.93 90.84 96.37 104.22 101.42 100.40 98.94 96.74
6 90.29 93.75 96.24 109.75 111.28 111.75 111.37 112.22 118.95 128.73 124.98 123.49 121.35 117.95
7 102.51 107.45 ≈ 111.93 ≈ 128.74 131.54 133.09 133.39 134.39 142.43 154.21 149.67 147.84 145.11 140.58
8 113.62 120.31 ≈ 126.39 ≈ 146.30 150.20 152.45 153.34 154.97 164.46 178.36 173.92 172.02 169.14 163.76
9 137.51 147.07 155.79 163.38 168.60 171.68 173.16 175.12 185.87 201.53 196.64 194.44 191.01 185.03
10 147.76 159.58 170.44 179.93 186.52 190.77 192.93 195.34 207.38 224.89 219.58 217.12 213.18 206.29

Standard ratings (EN 328 / Eurovent)

Standard condition Air inlet [°C] TD [K] High speed (Δ) [kW]Low speed (Y) [kW]
SC1 10 10 259.250219.583
SC2 0 8 181.887154.970
SC3 -18 7 150.492130.030
SC4 -25 6 111.26096.240
SC5 -34 6 102.82091.159

Dimensions

Dimension drawing of EK-SR-480BG4-A05 C
Dimension drawing
Dimensions as drawn
A 5660 mm
B 1360 mm
C 2790 mm
F 1310 mm
G 1770 mm
E 5265 mm
H 1393 mm
I 5690 mm
D IN 2 x Ø35
D OUT 2 x Ø66,7
Overall [mm]
Length 5660 mm
Width 1393 mm
Height 2790 mm

Downloads