Blast freezer EK-SR-491BC10-A04 C

Blast freezer EK-SR-491BC10-A04 C
Illustrative photo

Producer: Karyer · Line: EK-SR (Blast Freezers)

Product code: EK-SR-491BC10-A04 C

Cooling capacity i
78.57 kW
Air flow
115,569 m³/h
Fin spacing
10.0 mm
Fans
4 × ⌀910 mm

Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %

Data

Evaporator
Air flow 115,569 m³/h
External surface 253.9 m²
Inner volume 105.1 dm³
Fin spacing 10.0 mm
Fin materialAluminium
Net weight 1,104 kg
Fans
Quantity 4
Diameter 910 mm
Speed 840 rpm
Power 11,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 71.0 dB(A)
Sound power 96.0 dB(A)
Energy class E
Connections
Inlet Ø42
Outlet Ø66,7
Defrost
EK-SR-491BC10-A04 C None

Performance

TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.

R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)

High speed (Δ)
78.574 kW
Low speed (Y)
67.846 kW

Capacity matrix [kW]

R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.

≈ 1.23 estimate — vendor data irregular here

High speed (Δ)

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 32.27 31.96 31.82 31.66 31.28 30.77 30.19 30.14 31.75 34.07 32.87 32.42 31.79 30.85
5 37.52 38.04 38.43 42.99 42.84 42.35 41.71 41.77 44.16 47.48 45.84 45.21 44.30 42.90
6 45.49 46.95 47.89 54.25 54.64 54.54 54.05 54.21 57.35 61.75 59.66 58.90 57.80 56.12
7 52.25 54.51 56.55 64.81 66.04 66.71 66.82 67.16 71.13 76.77 74.39 73.46 72.10 69.92
8 58.30 61.51 ≈ 64.39 ≈ 74.31 76.14 77.23 77.74 78.57 83.44 90.50 88.40 87.56 86.31 84.25
9 70.95 75.65 79.88 83.58 86.12 87.71 88.57 89.63 95.23 103.38 101.07 100.12 98.69 96.30
10 76.55 82.47 87.85 92.56 95.89 98.11 99.38 100.72 107.07 116.35 113.87 112.82 111.23 108.55

Low speed (Y)

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 28.22 27.89 27.66 27.49 27.17 26.76 26.31 26.45 27.90 30.01 29.06 28.70 28.21 27.46
5 33.02 33.13 33.23 36.95 36.75 36.34 35.79 35.94 38.04 40.96 39.66 39.20 38.56 37.46
6 40.24 40.99 41.63 46.82 46.90 46.63 46.08 46.20 48.88 52.64 50.85 50.22 49.32 47.95
7 47.00 48.32 49.65 56.39 56.96 57.02 56.66 56.86 60.18 64.91 62.80 61.98 60.80 58.93
8 52.74 54.98 57.01 65.34 66.59 67.29 67.49 67.85 71.87 77.66 75.29 74.35 72.95 70.69
9 64.48 67.87 70.94 73.61 75.38 76.43 76.90 77.67 82.45 89.46 87.31 86.43 85.11 82.78
10 69.89 74.27 78.24 81.69 84.06 85.53 86.29 87.24 92.64 100.55 98.23 97.24 95.76 93.27

Standard ratings (EN 328 / Eurovent)

Standard condition Air inlet [°C] TD [K] High speed (Δ) [kW]Low speed (Y) [kW]
SC1 10 10 113.87398.225
SC2 0 8 78.57467.846
SC3 -18 7 65.37856.687
SC4 -25 6 47.88541.630
SC5 -34 6 45.87040.462

Dimensions

Dimension drawing of EK-SR-491BC10-A04 C
Dimension drawing
Dimensions as drawn
A 5660 mm
B 1360 mm
C 2790 mm
F 1310 mm
G 1770 mm
E 5265 mm
H 1393 mm
I 5690 mm
D IN 1 x Ø42
D OUT 1 x Ø66,7
Overall [mm]
Length 5660 mm
Width 1393 mm
Height 2790 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.