EK-T-491AE10-B04 C
113.60 kW
Defrost: None
Product code: EK-T-391AG10-B04 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 71,620 m³/h |
|---|---|
| External surface | 380.9 m² |
| Inner volume | 155.5 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 752 kg |
| Quantity | 3 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 8,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 72.0 dB(A) |
|---|---|
| Sound power | 96.1 dB(A) |
| Energy class | D |
| Inlet | Ø42 |
|---|---|
| Outlet | Ø66,7 |
| EK-T-391AG10-B04 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 51.63 | 50.56 | 49.86 | 49.39 | 48.72 | 47.93 | 47.06 | 47.72 | 50.60 | 54.48 | 52.87 | 52.27 | 51.43 | 50.16 |
| 5 | 60.48 | 59.89 | 59.45 | 65.84 | 65.21 | 64.27 | 63.12 | 63.56 | 67.31 | 72.55 | 70.23 | 69.45 | 68.35 | 66.71 |
| 6 | 74.08 | 74.25 | 74.52 | 83.08 | 82.69 | 81.72 | 80.43 | 80.65 | 85.29 | 91.85 | 88.60 | 87.43 | 85.75 | 83.22 |
| 7 | 87.12 | 88.34 | 89.47 | 100.48 | 100.36 | 99.72 | 98.47 | 98.55 | 104.13 | 112.18 | 108.12 | 106.57 | 104.30 | 100.71 |
| 8 | 99.44 | 101.53 | 103.76 | 117.39 | 118.23 | 118.01 | 116.97 | 117.05 | 123.71 | 133.41 | 128.63 | 126.74 | 123.92 | 119.39 |
| 9 | 122.01 | 126.01 | 129.72 | 133.04 | 134.98 | 135.71 | 135.57 | 135.88 | 143.69 | 155.01 | 149.74 | 147.54 | 144.27 | 138.87 |
| 10 | 133.12 | 138.64 | 143.64 | 148.06 | 150.62 | 151.92 | 152.11 | 153.14 | 162.25 | 175.54 | 170.67 | 168.55 | 164.95 | 158.74 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 42.24 | 41.24 | 40.66 | 40.33 | 39.87 | 39.32 | not rated | 39.47 | 41.98 | 45.43 | 44.36 | 44.02 | 43.45 | 42.54 |
| 5 | 49.11 | 48.35 | 47.94 | 53.02 | 52.52 | 51.79 | not rated | 51.49 | 54.60 | 58.97 | 57.18 | 56.58 | 55.76 | 54.59 |
| 6 | 60.37 | 59.90 | 59.66 | 66.30 | 65.87 | 65.07 | not rated | 64.34 | 68.08 | 73.42 | 70.87 | 69.95 | 68.64 | not rated |
| 7 | 71.26 | 71.33 | 71.62 | 79.96 | 79.71 | 78.90 | not rated | 77.85 | 82.27 | 88.69 | not rated | not rated | not rated | not rated |
| 8 | 81.76 | 82.57 | 83.46 | 93.66 | 93.74 | 93.11 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 9 | 102.00 | 103.90 | 105.71 | 107.06 | 107.53 | 107.18 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 10 | 112.46 | 115.10 | 117.97 | 120.47 | 121.47 | 121.45 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 170.672 | — |
| SC2 | 0 | 8 | 117.049 | — |
| SC3 | -18 | 7 | 100.620 | 79.928 |
| SC4 | -25 | 6 | 74.519 | 59.660 |
| SC5 | -34 | 6 | 74.226 | 60.340 |
| A | 4338 mm |
|---|---|
| C | 1287 mm |
| F | 1032 mm |
| G | 1150 mm |
| E1 | 1335 mm |
| E2 | 1300 mm |
| E | 3935 mm |
| H | 1354 mm |
| I | 1465 mm |
| D IN | 2 x Ø42 |
| D OUT | 2 x Ø66,7 |
| Length | 4338 mm |
|---|---|
| Width | 1354 mm |
| Height | 1465 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.