EA-G-430AE10-A01 C
9.06 kW
Defrost: None
Product code: EA-G-145BG9-A01 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
How to read the code of this model.
| Air flow | 4,708 m³/h |
|---|---|
| Air throw | 16 m |
| External surface | 28.5 m² |
| Inner volume | 16.7 dm³ |
| Fin spacing | 9.0 mm |
| Fin material | Aluminium |
| Net weight | 67 kg |
| Quantity | 1 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 490 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 75.0 dB(A) |
| Energy class | E |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| EA-G-145BG9-A01 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 3.96 | 3.57 | 3.49 | ≈ 3.39 |
| 8 | not rated | not rated | not rated | not rated | 6.14 | 5.94 | ≈ 5.95 | ≈ 7.60 |
| 10 | not rated | not rated | not rated | not rated | 8.31 | 8.98 | 10.09 | 11.20 |
| 12 | not rated | not rated | not rated | not rated | not rated | 12.01 | 13.22 | 14.51 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 8.976 | 2.82 | 64.3 |
| A | 1067 mm |
|---|---|
| B | 690 mm |
| C | 675 mm |
| F | 495 mm |
| E | 735 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 1067 mm |
|---|---|
| Width | 690 mm |
| Height | 675 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.