Skip to Content

Brine cooler EA-G-150AC10-A10 C

Brine cooler EA-G-150AC10-A10 C
Illustrative photo

Producer: Karyer · Line: EA-G (General)

Product code: EA-G-150AC10-A10 C

Cooling capacity i
6.04 kW
Air flow
7,462 m³/h
Fin spacing
10.0 mm
Air throw
20 m
Fans
1 × ⌀500 mm

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Data

Coil
Air flow 7,462 m³/h
Air throw 20 m
External surface 15.8 m²
Inner volume 9.3 dm³
Fin spacing 10.0 mm
Fin materialAluminium
Net weight 54 kg
Fans
Quantity 1
Diameter 500 mm
Speed 1,360 rpm
Power 690 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 58.0 dB(A)
Sound power 80.2 dB(A)
Energy class E
Connections
Inlet 1 1/2"
Outlet 1 1/2"
Defrost
EA-G-150AC10-A10 C None

Performance

Fluid -10 → -7 °C

ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.

ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)

Cooling capacity · High speed (Δ)
6.039 kW Sensible capacity 4.463 kW Fluid flow 1.90 m³/h Pressure drop 50.1 kPa
Cooling capacity · Low speed (Y)
4.809 kW Sensible capacity 3.554 kW Fluid flow 1.51 m³/h Pressure drop 33.5 kPa

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K

ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

≈ 1.23 estimate — vendor data irregular here

High speed (Δ)

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K
ΔT [K] \ air [°C] -25-20-15-10-50510
6 not rated not rated not rated not rated 2.40 2.11 2.12 ≈ 2.13
8 not rated not rated not rated not rated 3.84 3.66 ≈ 3.71 ≈ 5.13
10 not rated not rated not rated not rated 5.30 6.04 ≈ 7.00 7.95
12 not rated not rated not rated not rated not rated 8.45 9.44 10.52

Low speed (Y)

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K
ΔT [K] \ air [°C] -25-20-15-10-50510
6 not rated not rated not rated not rated 2.23 1.97 1.95 ≈ 1.95
8 not rated not rated not rated not rated 3.54 3.39 ≈ 3.43 ≈ 4.48
10 not rated not rated not rated not rated 4.87 4.81 ≈ 6.12 7.04
12 not rated not rated not rated not rated not rated 7.33 8.32 9.32

Nominal rating

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Fan connection Cooling capacity [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 6.039 1.90 50.1
Low speed (Y) 4.809 1.51 33.5

Dimensions

Dimension drawing of EA-G-150AC10-A10 C
Dimension drawing
Dimensions as drawn
A 1237 mm
B 590 mm
C 685 mm
F 395 mm
E 885 mm
D IN 1 1/2"
D OUT 1 1/2"
Overall [mm]
Length 1237 mm
Width 590 mm
Height 685 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.