EA-G-163EE10-A06 C
11.28 kW
Defrost: None
Product code: EA-G-150BC4-A10 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 7,109 m³/h |
|---|---|
| Air throw | 19 m |
| External surface | 37.9 m² |
| Inner volume | 11.3 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 61 kg |
| Quantity | 1 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,360 rpm |
| Power | 690 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 80.0 dB(A) |
| Energy class | E |
| Inlet | 1 1/2" |
|---|---|
| Outlet | 1 1/2" |
| EA-G-150BC4-A10 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 3.68 | 3.26 | ≈ 3.27 | ≈ 3.27 |
| 8 | not rated | not rated | not rated | not rated | 5.97 | ≈ 5.62 | ≈ 8.01 | ≈ 9.11 |
| 10 | not rated | not rated | not rated | not rated | 10.12 | 11.29 | 12.34 | 13.67 |
| 12 | not rated | not rated | not rated | not rated | not rated | 15.01 | 16.33 | 17.93 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 3.40 | 2.98 | ≈ 2.98 | ≈ 2.97 |
| 8 | not rated | not rated | not rated | not rated | 5.47 | ≈ 5.18 | ≈ 6.64 | ≈ 7.89 |
| 10 | not rated | not rated | not rated | not rated | ≈ 7.57 | 9.63 | 10.68 | 11.89 |
| 12 | not rated | not rated | not rated | not rated | not rated | 12.91 | 14.16 | 15.59 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 11.293 | 3.55 | 102.4 |
| Low speed (Y) | 9.629 | 3.02 | 77.3 |
| A | 1237 mm |
|---|---|
| B | 590 mm |
| C | 745 mm |
| F | 395 mm |
| E | 885 mm |
| D IN | 1 1/2" |
| D OUT | 1 1/2" |
| Length | 1237 mm |
|---|---|
| Width | 590 mm |
| Height | 745 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.