EA-G-435AE4-A01 C
11.98 kW
Defrost: None
Product code: EA-G-150BE7-A09 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 6,710 m³/h |
|---|---|
| Air throw | 18 m |
| External surface | 35.9 m² |
| Inner volume | 15.6 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 71 kg |
| Quantity | 1 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,330 rpm |
| Power | 710 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 78.0 dB(A) |
| Energy class | E |
| Inlet | 1 1/2" |
|---|---|
| Outlet | 1 1/2" |
| EA-G-150BE7-A09 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 4.53 | 4.02 | ≈ 3.91 | ≈ 3.83 |
| 8 | not rated | not rated | not rated | not rated | 7.14 | ≈ 6.85 | ≈ 8.58 | ≈ 9.83 |
| 10 | not rated | not rated | not rated | not rated | ≈ 10.04 | 11.98 | 13.06 | 14.36 |
| 12 | not rated | not rated | not rated | not rated | not rated | 15.67 | 17.02 | 18.60 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 11.984 | 3.76 | 103.6 |
| A | 1237 mm |
|---|---|
| B | 640 mm |
| C | 745 mm |
| F | 445 mm |
| E | 885 mm |
| D IN | 1 1/2" |
| D OUT | 1 1/2" |
| Length | 1237 mm |
|---|---|
| Width | 640 mm |
| Height | 745 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.