EA-G-530CC4-A05 C
11.57 kW
Defrost: None
Product code: EA-G-163ED7-A06 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 8,575 m³/h |
|---|---|
| Air throw | 20 m |
| External surface | 56.2 m² |
| Inner volume | 18.5 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 105 kg |
| Quantity | 1 |
|---|---|
| Diameter | 630 mm |
| Speed | 890 rpm |
| Power | 600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 51.0 dB(A) |
|---|---|
| Sound power | 73.1 dB(A) |
| Energy class | E |
| Inlet | 1 1/2" |
|---|---|
| Outlet | 1 1/2" |
| EA-G-163ED7-A06 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 4.18 | 3.73 | ≈ 3.74 | ≈ 3.77 |
| 8 | not rated | not rated | not rated | not rated | 6.70 | 7.34 | ≈ 8.41 | ≈ 9.12 |
| 10 | not rated | not rated | not rated | not rated | 10.80 | 11.58 | 12.37 | 13.53 |
| 12 | not rated | not rated | not rated | not rated | not rated | 15.25 | 16.30 | 17.71 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 3.84 | 3.37 | ≈ 3.37 | ≈ 3.36 |
| 8 | not rated | not rated | not rated | not rated | 6.10 | ≈ 5.77 | ≈ 7.25 | ≈ 7.97 |
| 10 | not rated | not rated | not rated | not rated | ≈ 8.60 | 9.98 | 10.78 | 11.84 |
| 12 | not rated | not rated | not rated | not rated | not rated | 13.21 | 14.23 | 15.48 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 11.584 | 3.64 | 82.0 |
| Low speed (Y) | 9.976 | 3.13 | 63.0 |
| A | 1215 mm |
|---|---|
| B | 950 mm |
| C | 1190 mm |
| F | 910 mm |
| E | 835 mm |
| D IN | 1 1/2" |
| D OUT | 1 1/2" |
| Length | 1215 mm |
|---|---|
| Width | 950 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.