Skip to Content

Brine cooler EA-G-163EG4-A11 C

Brine cooler EA-G-163EG4-A11 C
Illustrative photo

Producer: Karyer · Line: EA-G (General)

Product code: EA-G-163EG4-A11 C

Cooling capacity i
25.31 kW
Air flow
12,411 m³/h
Fin spacing
4.6 mm
Air throw
30 m
Fans
1 × ⌀630 mm

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Data

Coil
Air flow 12,411 m³/h
Air throw 30 m
External surface 133.7 m²
Inner volume 30.7 dm³
Fin spacing 4.6 mm
Fin materialAluminium
Net weight 139 kg
Fans
Quantity 1
Diameter 630 mm
Speed 1,330 rpm
Power 2,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 69.0 dB(A)
Sound power 91.5 dB(A)
Energy class E
Connections
Inlet 2"
Outlet 2"
Defrost
EA-G-163EG4-A11 C None

Performance

Fluid -10 → -7 °C

ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.

ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)

Cooling capacity · High speed (Δ)
25.308 kW Sensible capacity 18.265 kW Fluid flow 7.95 m³/h Pressure drop 80.7 kPa above the recommended pressure drop
Cooling capacity · Low speed (Y)
20.921 kW Sensible capacity 15.062 kW Fluid flow 6.57 m³/h Pressure drop 57.6 kPa

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K

ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

≈ 1.23 estimate — vendor data irregular here

High speed (Δ)

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K
ΔT [K] \ air [°C] -25-20-15-10-50510
6 not rated not rated not rated not rated 8.16 ≈ 7.47 ≈ 7.51 ≈ 8.46
8 not rated not rated not rated not rated ≈ 13.29 ≈ 15.52 ≈ 17.89 ≈ 19.82
10 not rated not rated not rated not rated 23.29 25.31 27.13 29.75
12 not rated not rated not rated not rated not rated 33.59 35.99 39.12

Low speed (Y)

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K
ΔT [K] \ air [°C] -25-20-15-10-50510
6 not rated not rated not rated not rated 7.45 6.67 ≈ 6.70 ≈ 6.66
8 not rated not rated not rated not rated 11.97 ≈ 11.27 ≈ 14.89 ≈ 16.71
10 not rated not rated not rated not rated 18.25 20.92 22.78 not rated
12 not rated not rated not rated not rated not rated 27.95 30.22 not rated

Nominal rating

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Fan connection Cooling capacity [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 25.308 7.95 80.7
Low speed (Y) 20.921 6.57 57.6

Dimensions

Dimension drawing of EA-G-163EG4-A11 C
Dimension drawing
Dimensions as drawn
A 1215 mm
B 1100 mm
C 1190 mm
F 1060 mm
E 835 mm
D IN 2"
D OUT 2"
Overall [mm]
Length 1215 mm
Width 1100 mm
Height 1190 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.