EA-G-250AE7-A10 C
19.78 kW
Defrost: None
Product code: EA-G-163FD4-A08 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 14,605 m³/h |
|---|---|
| Air throw | 34 m |
| External surface | 104.3 m² |
| Inner volume | 24.8 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 125 kg |
| Quantity | 1 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 1,900 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 70.0 dB(A) |
|---|---|
| Sound power | 92.0 dB(A) |
| Energy class | E |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| EA-G-163FD4-A08 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 5.89 | 5.51 | ≈ 5.55 | ≈ 5.56 |
| 8 | not rated | not rated | not rated | not rated | 9.77 | ≈ 9.04 | ≈ 13.66 | ≈ 15.40 |
| 10 | not rated | not rated | not rated | not rated | ≈ 17.06 | 19.77 | 21.57 | 24.07 |
| 12 | not rated | not rated | not rated | not rated | not rated | 27.04 | 29.26 | 32.17 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 5.52 | 5.08 | ≈ 5.10 | ≈ 5.11 |
| 8 | not rated | not rated | not rated | not rated | 9.07 | ≈ 8.44 | ≈ 11.47 | ≈ 13.37 |
| 10 | not rated | not rated | not rated | not rated | ≈ 12.73 | 16.79 | 18.72 | 21.04 |
| 12 | not rated | not rated | not rated | not rated | not rated | 23.30 | 25.48 | 28.11 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 19.766 | 6.21 | 54.4 |
| Low speed (Y) | 16.789 | 5.27 | 40.8 |
| A | 1415 mm |
|---|---|
| B | 950 mm |
| C | 1190 mm |
| F | 910 mm |
| G | 985 mm |
| E | 1035 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 1415 mm |
|---|---|
| Width | 950 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.