EA-G-163ED4-A06 C
14.02 kW
Defrost: None
Product code: EA-G-163GD10-A19 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 12,502 m³/h |
|---|---|
| Air throw | 28 m |
| External surface | 66.0 m² |
| Inner volume | 30.6 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 134 kg |
| Quantity | 1 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 1,250 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 62.0 dB(A) |
|---|---|
| Sound power | 84.7 dB(A) |
| Energy class | E |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| EA-G-163GD10-A19 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 5.31 | 4.68 | ≈ 4.68 | ≈ 4.68 |
| 8 | not rated | not rated | not rated | not rated | 8.51 | ≈ 8.02 | ≈ 9.90 | ≈ 11.51 |
| 10 | not rated | not rated | not rated | not rated | ≈ 11.75 | 14.03 | 15.72 | 17.59 |
| 12 | not rated | not rated | not rated | not rated | not rated | 19.18 | 21.02 | 23.18 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 4.97 | 4.36 | 4.33 | ≈ 4.31 |
| 8 | not rated | not rated | not rated | not rated | 7.90 | 7.48 | ≈ 7.55 | ≈ 10.19 |
| 10 | not rated | not rated | not rated | not rated | 10.86 | 10.63 | ≈ 13.95 | 15.71 |
| 12 | not rated | not rated | not rated | not rated | not rated | 16.91 | 18.74 | 20.72 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 14.031 | 4.41 | 36.4 |
| Low speed (Y) | 10.633 | 3.34 | 22.3 |
| A | 1715 mm |
|---|---|
| B | 950 mm |
| C | 1190 mm |
| F | 910 mm |
| E | 1335 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 1715 mm |
|---|---|
| Width | 950 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.