EA-G-263FC7-A19 C
25.51 kW
Defrost: None
Product code: EA-G-180GE10-A01 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 20,442 m³/h |
|---|---|
| Air throw | 38 m |
| External surface | 95.2 m² |
| Inner volume | 43.4 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 196 kg |
| Quantity | 1 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 1,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 57.0 dB(A) |
|---|---|
| Sound power | 80.0 dB(A) |
| Energy class | E |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| EA-G-180GE10-A01 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 8.64 | ≈ 7.70 | ≈ 7.72 | ≈ 7.70 |
| 8 | not rated | not rated | not rated | not rated | ≈ 13.88 | ≈ 16.43 | ≈ 18.67 | ≈ 20.25 |
| 10 | not rated | not rated | not rated | not rated | 23.83 | 25.55 | 27.30 | 29.87 |
| 12 | not rated | not rated | not rated | not rated | not rated | 33.48 | 35.84 | 38.93 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 7.77 | 6.83 | ≈ 6.81 | ≈ 6.78 |
| 8 | not rated | not rated | not rated | not rated | 12.35 | ≈ 11.71 | ≈ 15.45 | ≈ 16.99 |
| 10 | not rated | not rated | not rated | not rated | ≈ 16.97 | 21.08 | 22.89 | 25.13 |
| 12 | not rated | not rated | not rated | not rated | not rated | 27.84 | 30.05 | 32.74 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 25.546 | 8.02 | 78.0 |
| Low speed (Y) | 21.081 | 6.62 | 55.6 |
| A | 1715 mm |
|---|---|
| B | 1050 mm |
| C | 1430 mm |
| F | 1010 mm |
| G | 1100 mm |
| E | 1335 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 1715 mm |
|---|---|
| Width | 1050 mm |
| Height | 1430 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.