EA-G-445AE7-A01 C
33.19 kW
Defrost: None
Product code: EA-G-180GE4-A01 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 18,270 m³/h |
|---|---|
| Air throw | 35 m |
| External surface | 195.5 m² |
| Inner volume | 43.4 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 211 kg |
| Quantity | 1 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 1,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 80.8 dB(A) |
| Energy class | E |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| EA-G-180GE4-A01 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 9.93 | 9.16 | ≈ 9.21 | ≈ 9.20 |
| 8 | not rated | not rated | not rated | not rated | 16.31 | ≈ 15.17 | ≈ 23.25 | ≈ 26.23 |
| 10 | not rated | not rated | not rated | not rated | 29.31 | 33.24 | 36.12 | 39.99 |
| 12 | not rated | not rated | not rated | not rated | not rated | 44.71 | 48.31 | 52.87 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 9.02 | 8.13 | ≈ 8.16 | ≈ 8.13 |
| 8 | not rated | not rated | not rated | not rated | 14.63 | ≈ 13.71 | ≈ 17.95 | ≈ 21.49 |
| 10 | not rated | not rated | not rated | not rated | ≈ 20.37 | 26.37 | 29.52 | 33.01 |
| 12 | not rated | not rated | not rated | not rated | not rated | 36.15 | 39.63 | 43.60 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 33.238 | 10.44 | 58.5 |
| Low speed (Y) | 26.367 | 8.28 | 38.8 |
| A | 1715 mm |
|---|---|
| B | 1050 mm |
| C | 1430 mm |
| F | 1010 mm |
| G | 1100 mm |
| E | 1335 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 1715 mm |
|---|---|
| Width | 1050 mm |
| Height | 1430 mm |
Our engineers answer with a selection for your conditions.