Skip to Content

Brine cooler EA-G-250AE10-A10 C

Brine cooler EA-G-250AE10-A10 C
Illustrative photo

Producer: Karyer · Line: EA-G (General)

Product code: EA-G-250AE10-A10 C

Cooling capacity i
18.53 kW
Air flow
13,760 m³/h
Fin spacing
10.0 mm
Air throw
20 m
Fans
2 × ⌀500 mm

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Data

Coil
Air flow 13,760 m³/h
Air throw 20 m
External surface 47.0 m²
Inner volume 22.0 dm³
Fin spacing 10.0 mm
Fin materialAluminium
Net weight 108 kg
Fans
Quantity 2
Diameter 500 mm
Speed 1,360 rpm
Power 1,380 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 61.0 dB(A)
Sound power 83.0 dB(A)
Energy class E
Connections
Inlet 1 1/2"
Outlet 1 1/2"
Defrost
EA-G-250AE10-A10 C None

Performance

Fluid -10 → -7 °C

ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.

ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)

Cooling capacity · High speed (Δ)
18.525 kW Sensible capacity 13.516 kW Fluid flow 5.82 m³/h Pressure drop 96.8 kPa above the recommended pressure drop
Cooling capacity · Low speed (Y)
15.831 kW Sensible capacity 11.523 kW Fluid flow 4.97 m³/h Pressure drop 73.4 kPa above the recommended pressure drop

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K

ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

≈ 1.23 estimate — vendor data irregular here

High speed (Δ)

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K
ΔT [K] \ air [°C] -25-20-15-10-50510
6 not rated not rated not rated not rated 5.91 5.24 ≈ 5.27 ≈ 5.28
8 not rated not rated not rated not rated 9.52 ≈ 9.02 ≈ 13.65 ≈ 15.24
10 not rated not rated not rated not rated ≈ 13.19 18.53 20.25 22.42
12 not rated not rated not rated not rated not rated 24.32 26.51 29.15

Low speed (Y)

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K
ΔT [K] \ air [°C] -25-20-15-10-50510
6 not rated not rated not rated not rated 5.46 4.82 ≈ 4.80 ≈ 4.80
8 not rated not rated not rated not rated 8.72 ≈ 8.32 ≈ 11.54 ≈ 13.22
10 not rated not rated not rated not rated ≈ 12.01 15.83 17.54 19.50
12 not rated not rated not rated not rated not rated 20.96 23.00 25.35

Nominal rating

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Fan connection Cooling capacity [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 18.525 5.82 96.8
Low speed (Y) 15.831 4.97 73.4

Dimensions

Dimension drawing of EA-G-250AE10-A10 C
Dimension drawing
Dimensions as drawn
A 2087 mm
B 640 mm
C 685 mm
F 445 mm
E1 868 mm
E 1735 mm
D IN 1 1/2"
D OUT 1 1/2"
Overall [mm]
Length 2087 mm
Width 640 mm
Height 685 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.