EA-G-350AE10-A10 C
25.92 kW
Defrost: None
Product code: EA-G-250AE4-A10 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 12,115 m³/h |
|---|---|
| Air throw | 18 m |
| External surface | 103.5 m² |
| Inner volume | 23.3 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 116 kg |
| Quantity | 2 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,360 rpm |
| Power | 1,380 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 62.0 dB(A) |
|---|---|
| Sound power | 84.1 dB(A) |
| Energy class | E |
| Inlet | 1 1/2" |
|---|---|
| Outlet | 1 1/2" |
| EA-G-250AE4-A10 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 7.23 | 6.60 | ≈ 6.65 | ≈ 6.65 |
| 8 | not rated | not rated | not rated | not rated | 11.87 | ≈ 11.10 | ≈ 18.24 | ≈ 21.15 |
| 10 | not rated | not rated | not rated | not rated | 22.62 | 25.92 | 28.50 | 31.63 |
| 12 | not rated | not rated | not rated | not rated | not rated | 34.47 | 37.65 | 41.43 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 6.69 | 6.00 | ≈ 6.04 | ≈ 6.03 |
| 8 | not rated | not rated | not rated | not rated | 10.85 | ≈ 10.22 | ≈ 14.57 | ≈ 17.81 |
| 10 | not rated | not rated | not rated | not rated | ≈ 15.13 | 21.31 | 23.94 | 26.73 |
| 12 | not rated | not rated | not rated | not rated | not rated | 28.71 | 31.68 | 34.98 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 25.915 | 8.14 | 87.7 |
| Low speed (Y) | 21.308 | 6.69 | 62.0 |
| A | 2087 mm |
|---|---|
| B | 640 mm |
| C | 685 mm |
| F | 445 mm |
| E1 | 868 mm |
| E | 1735 mm |
| D IN | 1 1/2" |
| D OUT | 1 1/2" |
| Length | 2087 mm |
|---|---|
| Width | 640 mm |
| Height | 685 mm |
Our engineers answer with a selection for your conditions.