EA-G-163GE4-A19 C
23.42 kW
Defrost: None
Product code: EA-G-263EC7-A11 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 32,597 m³/h |
|---|---|
| Air throw | 42 m |
| External surface | 90.1 m² |
| Inner volume | 30.7 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 156 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 5,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 71.0 dB(A) |
|---|---|
| Sound power | 94.0 dB(A) |
| Energy class | E |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| EA-G-263EC7-A11 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 6.44 | 6.10 | ≈ 6.13 | ≈ 6.16 |
| 8 | not rated | not rated | not rated | not rated | ≈ 10.70 | ≈ 9.84 | ≈ 16.45 | ≈ 18.12 |
| 10 | not rated | not rated | not rated | not rated | ≈ 21.46 | 23.50 | 25.19 | 27.89 |
| 12 | not rated | not rated | not rated | not rated | not rated | 31.68 | 33.89 | 37.04 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 6.09 | 5.70 | ≈ 5.73 | ≈ 5.74 |
| 8 | not rated | not rated | not rated | not rated | 10.04 | ≈ 9.28 | ≈ 14.30 | ≈ 16.02 |
| 10 | not rated | not rated | not rated | not rated | ≈ 14.14 | 20.53 | 22.30 | 24.75 |
| 12 | not rated | not rated | not rated | not rated | not rated | 27.90 | 30.04 | 32.88 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 23.503 | 7.38 | 61.4 |
| Low speed (Y) | 20.532 | 6.45 | 48.3 |
| A | 2015 mm |
|---|---|
| B | 900 mm |
| C | 1190 mm |
| F | 860 mm |
| E1 | 818 mm |
| E | 1635 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 2015 mm |
|---|---|
| Width | 900 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.