EA-G-363EC7-A01 C
26.69 kW
Defrost: None
Product code: EA-G-263ED10-A11 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
How to read the code of this model.
| Air flow | 32,307 m³/h |
|---|---|
| Air throw | 41 m |
| External surface | 81.0 m² |
| Inner volume | 35.8 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 174 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 5,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 71.0 dB(A) |
|---|---|
| Sound power | 94.0 dB(A) |
| Energy class | E |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| EA-G-263ED10-A11 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 7.62 | ≈ 7.04 | ≈ 7.07 | ≈ 9.72 |
| 8 | not rated | not rated | not rated | not rated | ≈ 12.51 | ≈ 17.31 | ≈ 19.29 | ≈ 20.81 |
| 10 | not rated | not rated | not rated | not rated | ≈ 25.32 | 26.73 | 28.35 | 31.00 |
| 12 | not rated | not rated | not rated | not rated | not rated | 35.14 | 37.43 | 40.64 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 7.11 | ≈ 6.49 | ≈ 6.52 | ≈ 6.51 |
| 8 | not rated | not rated | not rated | not rated | ≈ 11.59 | ≈ 14.56 | ≈ 16.79 | ≈ 18.25 |
| 10 | not rated | not rated | not rated | not rated | 21.56 | 23.24 | 24.85 | 27.22 |
| 12 | not rated | not rated | not rated | not rated | not rated | 30.67 | 32.81 | 35.66 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 26.725 | 8.39 | 92.0 |
| Low speed (Y) | 23.242 | 7.30 | 71.9 |
| A | 2015 mm |
|---|---|
| B | 950 mm |
| C | 1190 mm |
| F | 910 mm |
| E1 | 818 mm |
| E | 1635 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 2015 mm |
|---|---|
| Width | 950 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.