EA-G-180GG10-A01 C
31.11 kW
Defrost: None
Product code: EA-G-263EE10-A11 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 31,036 m³/h |
|---|---|
| Air throw | 40 m |
| External surface | 97.7 m² |
| Inner volume | 43.4 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 186 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 5,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 71.0 dB(A) |
|---|---|
| Sound power | 93.5 dB(A) |
| Energy class | E |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| EA-G-263EE10-A11 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 9.19 | ≈ 8.45 | ≈ 8.48 | ≈ 10.99 |
| 8 | not rated | not rated | not rated | not rated | ≈ 15.03 | ≈ 19.83 | ≈ 22.43 | ≈ 24.27 |
| 10 | not rated | not rated | not rated | not rated | 29.14 | 31.05 | 33.04 | 36.16 |
| 12 | not rated | not rated | not rated | not rated | not rated | 40.88 | 43.63 | 47.38 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 8.52 | 7.72 | ≈ 7.74 | ≈ 7.72 |
| 8 | not rated | not rated | not rated | not rated | 13.80 | ≈ 12.93 | ≈ 19.22 | ≈ 21.05 |
| 10 | not rated | not rated | not rated | not rated | 24.22 | 26.61 | 28.62 | 31.43 |
| 12 | not rated | not rated | not rated | not rated | not rated | 35.23 | 37.83 | 41.17 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 31.045 | 9.75 | 82.2 |
| Low speed (Y) | 26.611 | 8.36 | 62.6 |
| A | 2015 mm |
|---|---|
| B | 1000 mm |
| C | 1190 mm |
| F | 960 mm |
| E1 | 818 mm |
| E | 1635 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 2015 mm |
|---|---|
| Width | 1000 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.