EA-G-363EC4-A01 C
32.77 kW
Defrost: None
Product code: EA-G-263EE4-A01 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 14,864 m³/h |
|---|---|
| Air throw | 20 m |
| External surface | 200.5 m² |
| Inner volume | 43.4 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 201 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 1,200 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 55.0 dB(A) |
|---|---|
| Sound power | 78.1 dB(A) |
| Energy class | E |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| EA-G-263EE4-A01 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 9.56 | ≈ 8.68 | ≈ 8.71 | ≈ 11.55 |
| 8 | not rated | not rated | not rated | not rated | ≈ 15.57 | ≈ 21.51 | ≈ 23.62 | ≈ 25.97 |
| 10 | not rated | not rated | not rated | not rated | 30.73 | 32.73 | 34.93 | 38.11 |
| 12 | not rated | not rated | not rated | not rated | not rated | 42.72 | 45.74 | 49.62 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 32.732 | 10.28 | 90.3 |
| A | 2015 mm |
|---|---|
| B | 1000 mm |
| C | 1190 mm |
| F | 960 mm |
| E1 | 818 mm |
| E | 1635 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 2015 mm |
|---|---|
| Width | 1000 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.