EA-G-550AC10-A10 C
30.13 kW
Defrost: None
Product code: EA-G-263FD10-A08 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 31,593 m³/h |
|---|---|
| Air throw | 40 m |
| External surface | 101.7 m² |
| Inner volume | 45.0 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 198 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 3,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 72.0 dB(A) |
|---|---|
| Sound power | 95.0 dB(A) |
| Energy class | E |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| EA-G-263FD10-A08 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 8.74 | ≈ 8.00 | ≈ 8.03 | ≈ 10.51 |
| 8 | not rated | not rated | not rated | not rated | ≈ 14.29 | ≈ 19.26 | ≈ 21.79 | ≈ 23.63 |
| 10 | not rated | not rated | not rated | not rated | 28.22 | 30.08 | 32.06 | 35.12 |
| 12 | not rated | not rated | not rated | not rated | not rated | 39.55 | 42.27 | 45.96 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 8.19 | 7.40 | ≈ 7.42 | ≈ 7.41 |
| 8 | not rated | not rated | not rated | not rated | 13.29 | ≈ 12.42 | ≈ 19.07 | ≈ 20.88 |
| 10 | not rated | not rated | not rated | not rated | 24.04 | 26.31 | 28.34 | 31.10 |
| 12 | not rated | not rated | not rated | not rated | not rated | 34.75 | 37.35 | 40.70 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 30.077 | 9.45 | 78.4 |
| Low speed (Y) | 26.305 | 8.26 | 61.8 |
| A | 2415 mm |
|---|---|
| B | 950 mm |
| C | 1190 mm |
| F | 910 mm |
| G | 985 mm |
| E1 | 1018 mm |
| E | 2035 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 2415 mm |
|---|---|
| Width | 950 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.