EA-G-540AG4-A01 C
34.93 kW
Defrost: None
Product code: EA-G-263FD7-A08 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 30,635 m³/h |
|---|---|
| Air throw | 39 m |
| External surface | 140.8 m² |
| Inner volume | 45.0 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 200 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 3,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 72.0 dB(A) |
|---|---|
| Sound power | 95.0 dB(A) |
| Energy class | E |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| EA-G-263FD7-A08 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | ≈ 9.41 | ≈ 8.76 | ≈ 8.80 | ≈ 13.06 |
| 8 | not rated | not rated | not rated | not rated | ≈ 21.12 | ≈ 23.00 | ≈ 25.30 | ≈ 27.13 |
| 10 | not rated | not rated | not rated | not rated | 33.38 | 34.95 | 36.87 | 40.18 |
| 12 | not rated | not rated | not rated | not rated | not rated | 45.76 | 48.55 | 52.61 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 8.85 | ≈ 8.13 | ≈ 8.16 | ≈ 10.91 |
| 8 | not rated | not rated | not rated | not rated | ≈ 14.46 | ≈ 19.77 | ≈ 22.24 | ≈ 24.01 |
| 10 | not rated | not rated | not rated | not rated | 28.83 | 30.64 | 32.57 | 35.57 |
| 12 | not rated | not rated | not rated | not rated | not rated | 40.24 | 42.89 | 46.53 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 34.945 | 10.98 | 102.2 |
| Low speed (Y) | 30.641 | 9.62 | 81.0 |
| A | 2415 mm |
|---|---|
| B | 950 mm |
| C | 1190 mm |
| F | 910 mm |
| G | 985 mm |
| E1 | 1018 mm |
| E | 2035 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 2415 mm |
|---|---|
| Width | 950 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.