Skip to Content

Brine cooler EA-G-263GC10-A19 C

Brine cooler EA-G-263GC10-A19 C
Illustrative photo

Producer: Karyer · Line: EA-G (General)

Product code: EA-G-263GC10-A19 C

Cooling capacity i
25.06 kW
Air flow
25,359 m³/h
Fin spacing
10.0 mm
Air throw
32 m
Fans
2 × ⌀630 mm

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Data

Coil
Air flow 25,359 m³/h
Air throw 32 m
External surface 105.8 m²
Inner volume 46.6 dm³
Fin spacing 10.0 mm
Fin materialAluminium
Net weight 205 kg
Fans
Quantity 2
Diameter 630 mm
Speed 1,330 rpm
Power 2,500 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 65.0 dB(A)
Sound power 88.1 dB(A)
Energy class E
Connections
Inlet 2"
Outlet 2"
Defrost
EA-G-263GC10-A19 C None

Performance

Fluid -10 → -7 °C

ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.

ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)

Cooling capacity · High speed (Δ)
25.062 kW Sensible capacity 18.433 kW Fluid flow 7.87 m³/h Pressure drop 57.2 kPa
Cooling capacity · Low speed (Y)
22.330 kW Sensible capacity 16.389 kW Fluid flow 7.01 m³/h Pressure drop 46.7 kPa

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K

ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

≈ 1.23 estimate — vendor data irregular here

High speed (Δ)

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K
ΔT [K] \ air [°C] -25-20-15-10-50510
6 not rated not rated not rated not rated 7.66 6.88 ≈ 6.89 ≈ 6.89
8 not rated not rated not rated not rated 12.43 ≈ 11.60 ≈ 18.22 ≈ 20.07
10 not rated not rated not rated not rated ≈ 17.32 25.06 27.11 29.89
12 not rated not rated not rated not rated not rated 33.12 35.74 39.09

Low speed (Y)

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K
ΔT [K] \ air [°C] -25-20-15-10-50510
6 not rated not rated not rated not rated 7.25 6.43 ≈ 6.44 ≈ 6.44
8 not rated not rated not rated not rated 11.70 ≈ 10.96 ≈ 16.19 ≈ 18.12
10 not rated not rated not rated not rated ≈ 16.24 22.33 24.46 27.08
12 not rated not rated not rated not rated not rated 29.73 32.30 35.42

Nominal rating

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Fan connection Cooling capacity [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 25.062 7.87 57.2
Low speed (Y) 22.330 7.01 46.7

Dimensions

Dimension drawing of EA-G-263GC10-A19 C
Dimension drawing
Dimensions as drawn
A 3015 mm
B 900 mm
C 1190 mm
F 860 mm
E1 1318 mm
E 2635 mm
D IN 2"
D OUT 2"
Overall [mm]
Length 3015 mm
Width 900 mm
Height 1190 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.