Skip to Content

Brine cooler EA-G-263GG10-A19 C

Brine cooler EA-G-263GG10-A19 C
Illustrative photo

Producer: Karyer · Line: EA-G (General)

Product code: EA-G-263GG10-A19 C

Cooling capacity i
47.25 kW
Air flow
23,967 m³/h
Fin spacing
10.0 mm
Air throw
30 m
Fans
2 × ⌀630 mm

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Model nomenclature

How to read the code of this model.

  • B
    Number of fans: 2 — Digit 1-9.
  • C
    Fan diameter: 63 — Ø630 mm
  • E
    Coil tube rows (2nd dimensional letter): G — 8 tube rows
  • F
    Fin spacing: 10 — 10.0 mm
  • G
    Generation code: A — generation A
  • H
    Fan data (fan motor code): 19 — three-phase 400 V 50 Hz, 4-pole AC fan (in this series)

Data

Coil
Air flow 23,967 m³/h
Air throw 30 m
External surface 211.6 m²
Inner volume 91.7 dm³
Fin spacing 10.0 mm
Fin materialAluminium
Net weight 300 kg
Fans
Quantity 2
Diameter 630 mm
Speed 1,330 rpm
Power 2,500 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 64.0 dB(A)
Sound power 87.0 dB(A)
Energy class E
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
EA-G-263GG10-A19 C None

Performance

Fluid -10 → -7 °C

ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.

ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)

Cooling capacity · High speed (Δ)
47.251 kW Sensible capacity 34.130 kW Fluid flow 14.84 m³/h Pressure drop 94.2 kPa above the recommended pressure drop
Cooling capacity · Low speed (Y)
40.764 kW Sensible capacity 29.384 kW Fluid flow 12.80 m³/h Pressure drop 72.5 kPa above the recommended pressure drop

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K

ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

≈ 1.23 estimate — vendor data irregular here

High speed (Δ)

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K
ΔT [K] \ air [°C] -25-20-15-10-50510
6 not rated not rated not rated not rated 15.09 ≈ 13.23 ≈ 13.23 ≈ 18.15
8 not rated not rated not rated not rated ≈ 24.09 ≈ 32.28 ≈ 34.57 ≈ 38.13
10 not rated not rated not rated not rated 44.85 47.25 50.36 54.85
12 not rated not rated not rated not rated not rated 60.79 65.13 70.69

Low speed (Y)

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K
ΔT [K] \ air [°C] -25-20-15-10-50510
6 not rated not rated not rated not rated 13.91 ≈ 12.23 ≈ 12.01 ≈ 11.96
8 not rated not rated not rated not rated ≈ 22.02 ≈ 27.22 ≈ 29.75 ≈ 33.26
10 not rated not rated not rated not rated 37.98 40.76 43.84 47.83
12 not rated not rated not rated not rated not rated 52.57 56.62 61.58

Nominal rating

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Fan connection Cooling capacity [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 47.251 14.84 94.2
Low speed (Y) 40.764 12.80 72.5

Dimensions

Dimension drawing of EA-G-263GG10-A19 C
Dimension drawing
Dimensions as drawn
A 3015 mm
B 1100 mm
C 1190 mm
F 1060 mm
E1 1318 mm
E 2635 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 3015 mm
Width 1100 mm
Height 1190 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.