EA-G-280GC7-A01 C
36.53 kW
Defrost: None
Product code: EA-G-280GC10-A01 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 44,065 m³/h |
|---|---|
| Air throw | 44 m |
| External surface | 127.0 m² |
| Inner volume | 55.8 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 294 kg |
| Quantity | 2 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 3,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 60.0 dB(A) |
|---|---|
| Sound power | 83.0 dB(A) |
| Energy class | E |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| EA-G-280GC10-A01 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 10.09 | ≈ 9.26 | ≈ 9.29 | ≈ 12.94 |
| 8 | not rated | not rated | not rated | not rated | ≈ 16.53 | ≈ 23.68 | ≈ 26.54 | ≈ 28.72 |
| 10 | not rated | not rated | not rated | not rated | ≈ 34.47 | 36.55 | 38.95 | 42.56 |
| 12 | not rated | not rated | not rated | not rated | not rated | 47.93 | 51.18 | 55.62 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 9.32 | 8.43 | ≈ 8.44 | ≈ 8.44 |
| 8 | not rated | not rated | not rated | not rated | 15.15 | ≈ 14.15 | ≈ 22.56 | ≈ 24.69 |
| 10 | not rated | not rated | not rated | not rated | 28.33 | 31.00 | 33.41 | 36.67 |
| 12 | not rated | not rated | not rated | not rated | not rated | 40.88 | 43.97 | 47.92 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 36.549 | 11.48 | 82.7 |
| Low speed (Y) | 31.000 | 9.74 | 61.8 |
| A | 3015 mm |
|---|---|
| B | 950 mm |
| C | 1430 mm |
| F | 910 mm |
| G | 1015 mm |
| E1 | 1318 mm |
| E | 2635 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 3015 mm |
|---|---|
| Width | 950 mm |
| Height | 1430 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.