Skip to Content

Brine cooler EA-G-280GG4-A01 C

Brine cooler EA-G-280GG4-A01 C
Illustrative photo

Producer: Karyer · Line: EA-G (General)

Product code: EA-G-280GG4-A01 C

Cooling capacity i
74.14 kW
Air flow
33,279 m³/h
Fin spacing
4.6 mm
Air throw
35 m
Fans
2 × ⌀800 mm

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Data

Coil
Air flow 33,279 m³/h
Air throw 35 m
External surface 521.3 m²
Inner volume 109.8 dm³
Fin spacing 4.6 mm
Fin materialAluminium
Net weight 445 kg
Fans
Quantity 2
Diameter 800 mm
Speed 900 rpm
Power 3,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 61.0 dB(A)
Sound power 84.3 dB(A)
Energy class E
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
EA-G-280GG4-A01 C None

Performance

Fluid -10 → -7 °C

ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.

ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)

Cooling capacity · High speed (Δ)
74.135 kW Sensible capacity 53.393 kW Fluid flow 23.28 m³/h Pressure drop 42.4 kPa
Cooling capacity · Low speed (Y)
40.812 kW Sensible capacity 29.580 kW Fluid flow 12.82 m³/h Pressure drop 14.6 kPa

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K

ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

≈ 1.23 estimate — vendor data irregular here

High speed (Δ)

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K
ΔT [K] \ air [°C] -25-20-15-10-50510
6 not rated not rated not rated not rated 20.41 18.95 ≈ 19.03 ≈ 19.00
8 not rated not rated not rated not rated 33.65 ≈ 31.15 ≈ 51.61 ≈ 60.03
10 not rated not rated not rated not rated ≈ 47.47 74.14 82.42 91.88
12 not rated not rated not rated not rated not rated 101.00 110.34 121.20

Low speed (Y)

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K
ΔT [K] \ air [°C] -25-20-15-10-50510
6 not rated not rated not rated not rated 18.57 16.84 16.88 ≈ 16.80
8 not rated not rated not rated not rated 30.17 28.20 ≈ 28.02 ≈ 47.22
10 not rated not rated not rated not rated 42.12 40.81 ≈ 64.90 73.47
12 not rated not rated not rated not rated not rated 78.57 87.69 96.90

Nominal rating

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Fan connection Cooling capacity [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 74.135 23.28 42.4
Low speed (Y) 40.812 12.82 14.6

Dimensions

Dimension drawing of EA-G-280GG4-A01 C
Dimension drawing
Dimensions as drawn
A 3015 mm
B 1150 mm
C 1430 mm
F 1110 mm
G 1215 mm
E1 1318 mm
E 2635 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 3015 mm
Width 1150 mm
Height 1430 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.