EA-G-530AC10-A05 C
5.52 kW
Defrost: None
Product code: EA-G-335AC10-A01 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 7,678 m³/h |
|---|---|
| Air throw | 12 m |
| External surface | 20.9 m² |
| Inner volume | 11.2 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 63 kg |
| Quantity | 3 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 495 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 75.0 dB(A) |
| Energy class | E |
| Inlet | 1 1/2" |
|---|---|
| Outlet | 1 1/2" |
| EA-G-335AC10-A01 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 2.51 | 2.23 | 2.24 | 2.25 |
| 8 | not rated | not rated | not rated | not rated | 4.06 | 3.84 | 3.87 | ≈ 3.88 |
| 10 | not rated | not rated | not rated | not rated | 5.63 | 5.52 | ≈ 5.52 | ≈ 8.67 |
| 12 | not rated | not rated | not rated | not rated | not rated | ≈ 7.21 | ≈ 10.24 | 11.72 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 5.516 | 1.73 | 16.5 |
| A | 1857 mm |
|---|---|
| B | 523 mm |
| C | 525 mm |
| F | 345 mm |
| E1 | 518 mm |
| E2 | 500 mm |
| E | 1535 mm |
| D IN | 1 1/2" |
| D OUT | 1 1/2" |
| Length | 1857 mm |
|---|---|
| Width | 523 mm |
| Height | 525 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.