EA-G-335AE4-A01 C
14.60 kW
Defrost: None
Product code: EA-G-335BG7-A01 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 6,056 m³/h |
|---|---|
| Air throw | 10 m |
| External surface | 58.8 m² |
| Inner volume | 23.8 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 98 kg |
| Quantity | 3 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 495 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 75.0 dB(A) |
| Energy class | D |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| EA-G-335BG7-A01 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 5.59 | 5.00 | ≈ 4.86 | ≈ 4.68 |
| 8 | not rated | not rated | not rated | not rated | 8.77 | ≈ 8.42 | ≈ 10.59 | ≈ 12.30 |
| 10 | not rated | not rated | not rated | not rated | ≈ 11.93 | 14.64 | 16.19 | 17.80 |
| 12 | not rated | not rated | not rated | not rated | not rated | 19.20 | 20.99 | 22.92 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 14.635 | 4.60 | 67.4 |
| A | 1857 mm |
|---|---|
| B | 673 mm |
| C | 535 mm |
| F | 495 mm |
| E1 | 518 mm |
| E2 | 500 mm |
| E | 1535 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 1857 mm |
|---|---|
| Width | 673 mm |
| Height | 535 mm |
Our engineers answer with a selection for your conditions.