EA-G-250BG4-A10 C
34.38 kW
Defrost: None
Product code: EA-G-350AG10-A09 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 18,536 m³/h |
|---|---|
| Air throw | 19 m |
| External surface | 95.0 m² |
| Inner volume | 45.7 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 189 kg |
| Quantity | 3 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,330 rpm |
| Power | 2,130 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 83.0 dB(A) |
| Energy class | E |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| EA-G-350AG10-A09 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 10.84 | ≈ 9.55 | ≈ 9.56 | ≈ 9.55 |
| 8 | not rated | not rated | not rated | not rated | ≈ 17.32 | ≈ 23.25 | ≈ 25.37 | ≈ 28.55 |
| 10 | not rated | not rated | not rated | not rated | 31.99 | 34.61 | 37.44 | 41.04 |
| 12 | not rated | not rated | not rated | not rated | not rated | 44.63 | 48.34 | 52.81 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 34.607 | 10.87 | 120.6 |
| A | 2937 mm |
|---|---|
| B | 740 mm |
| C | 715 mm |
| F | 660 mm |
| E1 | 868 mm |
| E2 | 850 mm |
| E | 2585 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 2937 mm |
|---|---|
| Width | 740 mm |
| Height | 715 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.