EA-G-363FC10-A08 C
35.27 kW
Defrost: None
Product code: EA-G-350AG10-A10 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
How to read the code of this model.
| Air flow | 19,122 m³/h |
|---|---|
| Air throw | 20 m |
| External surface | 95.0 m² |
| Inner volume | 45.7 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 189 kg |
| Quantity | 3 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,360 rpm |
| Power | 2,070 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 64.0 dB(A) |
|---|---|
| Sound power | 86.0 dB(A) |
| Energy class | E |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| EA-G-350AG10-A10 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 10.96 | ≈ 9.65 | ≈ 9.69 | ≈ 13.54 |
| 8 | not rated | not rated | not rated | not rated | ≈ 17.53 | ≈ 23.80 | ≈ 25.90 | ≈ 29.07 |
| 10 | not rated | not rated | not rated | not rated | 32.72 | 35.30 | 38.14 | 41.78 |
| 12 | not rated | not rated | not rated | not rated | not rated | 45.51 | 49.25 | 53.76 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 10.01 | 8.89 | ≈ 8.71 | ≈ 8.68 |
| 8 | not rated | not rated | not rated | not rated | 15.86 | ≈ 15.18 | ≈ 21.83 | ≈ 24.82 |
| 10 | not rated | not rated | not rated | not rated | ≈ 21.75 | 29.77 | 32.48 | 35.68 |
| 12 | not rated | not rated | not rated | not rated | not rated | 38.56 | 41.95 | 45.87 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 35.303 | 11.09 | 124.9 |
| Low speed (Y) | 29.766 | 9.35 | 92.4 |
| A | 2937 mm |
|---|---|
| B | 740 mm |
| C | 715 mm |
| F | 660 mm |
| E1 | 868 mm |
| E2 | 850 mm |
| E | 2585 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 2937 mm |
|---|---|
| Width | 740 mm |
| Height | 715 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.