EA-G-263EE10-A01 C
21.90 kW
Defrost: None
Product code: EA-G-350BC9-A10 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 22,926 m³/h |
|---|---|
| Air throw | 23 m |
| External surface | 57.5 m² |
| Inner volume | 29.6 dm³ |
| Fin spacing | 9.0 mm |
| Fin material | Aluminium |
| Net weight | 140 kg |
| Quantity | 3 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,360 rpm |
| Power | 2,070 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 63.0 dB(A) |
|---|---|
| Sound power | 85.5 dB(A) |
| Energy class | E |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| EA-G-350BC9-A10 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 6.72 | 5.97 | ≈ 5.98 | ≈ 5.97 |
| 8 | not rated | not rated | not rated | not rated | 10.92 | ≈ 10.26 | ≈ 15.45 | ≈ 18.16 |
| 10 | not rated | not rated | not rated | not rated | ≈ 15.24 | 21.91 | 24.53 | 27.45 |
| 12 | not rated | not rated | not rated | not rated | not rated | 29.60 | 32.61 | 36.00 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 6.28 | 5.52 | 5.52 | ≈ 5.50 |
| 8 | not rated | not rated | not rated | not rated | 10.14 | 9.58 | ≈ 9.42 | ≈ 15.82 |
| 10 | not rated | not rated | not rated | not rated | 14.08 | 13.76 | ≈ 21.41 | 24.14 |
| 12 | not rated | not rated | not rated | not rated | not rated | 25.66 | 28.60 | 31.68 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 21.905 | 6.88 | 57.7 |
| Low speed (Y) | 13.763 | 4.32 | 25.4 |
| A | 2937 mm |
|---|---|
| B | 590 mm |
| C | 775 mm |
| F | 510 mm |
| E1 | 868 mm |
| E2 | 850 mm |
| E | 2585 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 2937 mm |
|---|---|
| Width | 590 mm |
| Height | 775 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.