EA-G-263EG4-A01 C
36.82 kW
Defrost: None
Product code: EA-G-363EE10-A06 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 25,680 m³/h |
|---|---|
| Air throw | 23 m |
| External surface | 146.5 m² |
| Inner volume | 66.3 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 261 kg |
| Quantity | 3 |
|---|---|
| Diameter | 630 mm |
| Speed | 890 rpm |
| Power | 1,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 55.0 dB(A) |
|---|---|
| Sound power | 78.1 dB(A) |
| Energy class | E |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| EA-G-363EE10-A06 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 11.23 | ≈ 10.04 | ≈ 10.06 | ≈ 13.29 |
| 8 | not rated | not rated | not rated | not rated | ≈ 18.11 | ≈ 24.84 | ≈ 27.38 | ≈ 29.30 |
| 10 | not rated | not rated | not rated | not rated | 34.96 | 36.84 | 39.13 | 42.55 |
| 12 | not rated | not rated | not rated | not rated | not rated | 47.69 | 50.89 | 55.10 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 10.35 | ≈ 9.11 | ≈ 9.11 | ≈ 9.08 |
| 8 | not rated | not rated | not rated | not rated | ≈ 16.55 | ≈ 20.75 | ≈ 23.05 | ≈ 25.43 |
| 10 | not rated | not rated | not rated | not rated | 29.45 | 31.61 | 33.93 | 36.92 |
| 12 | not rated | not rated | not rated | not rated | not rated | 41.06 | 44.08 | 47.75 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 36.839 | 11.57 | 92.7 |
| Low speed (Y) | 31.613 | 9.93 | 70.8 |
| A | 2815 mm |
|---|---|
| B | 1000 mm |
| C | 1190 mm |
| F | 960 mm |
| E1 | 818 mm |
| E2 | 800 mm |
| E | 2435 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 2815 mm |
|---|---|
| Width | 1000 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.