Skip to Content

Brine cooler EA-G-363EE10-A11 C

Brine cooler EA-G-363EE10-A11 C
Illustrative photo

Producer: Karyer · Line: EA-G (General)

Product code: EA-G-363EE10-A11 C

Cooling capacity i
46.39 kW
Air flow
46,555 m³/h
Fin spacing
10.0 mm
Air throw
42 m
Fans
3 × ⌀630 mm

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Model nomenclature

How to read the code of this model.

  • B
    Number of fans: 3 — Digit 1-9.
  • C
    Fan diameter: 63 — Ø630 mm
  • E
    Coil tube rows (2nd dimensional letter): E — 6 tube rows
  • F
    Fin spacing: 10 — 10.0 mm
  • G
    Generation code: A — generation A
  • H
    Fan data (fan motor code): 11 — three-phase 400 V 50 Hz, 4-pole AC fan (in this series)

Data

Coil
Air flow 46,555 m³/h
Air throw 42 m
External surface 146.5 m²
Inner volume 66.3 dm³
Fin spacing 10.0 mm
Fin materialAluminium
Net weight 261 kg
Fans
Quantity 3
Diameter 630 mm
Speed 1,330 rpm
Power 7,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 73.0 dB(A)
Sound power 95.5 dB(A)
Energy class E
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
EA-G-363EE10-A11 C None

Performance

Fluid -10 → -7 °C

ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.

ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)

Cooling capacity · High speed (Δ)
46.390 kW Sensible capacity 34.112 kW Fluid flow 14.57 m³/h Pressure drop 76.2 kPa above the recommended pressure drop
Cooling capacity · Low speed (Y)
39.755 kW Sensible capacity 29.129 kW Fluid flow 12.49 m³/h Pressure drop 58.0 kPa

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K

ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

≈ 1.23 estimate — vendor data irregular here

High speed (Δ)

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K
ΔT [K] \ air [°C] -25-20-15-10-50510
6 not rated not rated not rated not rated 12.36 ≈ 11.50 ≈ 11.55 ≈ 16.33
8 not rated not rated not rated not rated ≈ 20.37 ≈ 29.50 ≈ 33.48 ≈ 36.27
10 not rated not rated not rated not rated ≈ 43.48 46.39 49.41 54.10
12 not rated not rated not rated not rated not rated 61.15 65.29 70.94

Low speed (Y)

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K
ΔT [K] \ air [°C] -25-20-15-10-50510
6 not rated not rated not rated not rated 11.53 10.58 ≈ 10.62 ≈ 10.60
8 not rated not rated not rated not rated 18.85 ≈ 17.55 ≈ 28.68 ≈ 31.45
10 not rated not rated not rated not rated 36.08 39.76 42.80 47.03
12 not rated not rated not rated not rated not rated 52.69 56.61 61.64

Nominal rating

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Fan connection Cooling capacity [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 46.390 14.57 76.2
Low speed (Y) 39.755 12.49 58.0

Dimensions

Dimension drawing of EA-G-363EE10-A11 C
Dimension drawing
Dimensions as drawn
A 2815 mm
B 1000 mm
C 1190 mm
F 960 mm
E1 818 mm
E2 800 mm
E 2435 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 2815 mm
Width 1000 mm
Height 1190 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.