EA-G-380GC10-A01 C
56.99 kW
Defrost: None
Product code: EA-G-363FC4-A08 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 45,877 m³/h |
|---|---|
| Air throw | 41 m |
| External surface | 250.3 m² |
| Inner volume | 51.8 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 264 kg |
| Quantity | 3 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 5,700 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 74.0 dB(A) |
|---|---|
| Sound power | 97.0 dB(A) |
| Energy class | E |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| EA-G-363FC4-A08 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | ≈ 10.98 | ≈ 10.60 | ≈ 18.72 | ≈ 21.49 |
| 8 | not rated | not rated | not rated | not rated | ≈ 35.72 | ≈ 37.42 | ≈ 40.82 | ≈ 43.64 |
| 10 | not rated | not rated | not rated | not rated | 54.56 | 56.77 | 59.79 | 65.23 |
| 12 | not rated | not rated | not rated | not rated | not rated | 74.65 | 79.15 | 85.85 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | ≈ 10.50 | ≈ 10.01 | ≈ 10.08 | ≈ 18.30 |
| 8 | not rated | not rated | not rated | not rated | ≈ 29.68 | ≈ 32.53 | ≈ 36.09 | ≈ 38.70 |
| 10 | not rated | not rated | not rated | not rated | 47.43 | 49.92 | 52.88 | 57.78 |
| 12 | not rated | not rated | not rated | not rated | not rated | 65.67 | 69.94 | 75.94 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 56.771 | 17.82 | 136.1 |
| Low speed (Y) | 49.917 | 15.68 | 108.4 |
| A | 3415 mm |
|---|---|
| B | 900 mm |
| C | 1190 mm |
| F | 860 mm |
| G | 935 mm |
| E1 | 1018 mm |
| E2 | 1000 mm |
| E | 3035 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 3415 mm |
|---|---|
| Width | 900 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.