EA-G-663EC7-A11 C
71.31 kW
Defrost: None
Product code: EA-G-380GC4-A01 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 61,327 m³/h |
|---|---|
| Air throw | 43 m |
| External surface | 390.9 m² |
| Inner volume | 85.0 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 453 kg |
| Quantity | 3 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 5,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 85.0 dB(A) |
| Energy class | E |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| EA-G-380GC4-A01 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 14.23 | 14.38 | ≈ 14.48 | ≈ 14.55 |
| 8 | not rated | not rated | not rated | not rated | ≈ 23.59 | ≈ 23.52 | ≈ 49.37 | ≈ 55.14 |
| 10 | not rated | not rated | not rated | not rated | ≈ 63.17 | 71.08 | 77.09 | 85.81 |
| 12 | not rated | not rated | not rated | not rated | not rated | 96.69 | 104.33 | 114.52 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 13.25 | 13.39 | ≈ 13.47 | ≈ 13.50 |
| 8 | not rated | not rated | not rated | not rated | 22.14 | ≈ 21.66 | ≈ 40.35 | ≈ 46.62 |
| 10 | not rated | not rated | not rated | not rated | ≈ 31.69 | 58.75 | 65.17 | 73.04 |
| 12 | not rated | not rated | not rated | not rated | not rated | 81.09 | 88.44 | 97.44 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 71.076 | 22.33 | 59.2 |
| Low speed (Y) | 58.745 | 18.45 | 42.1 |
| A | 4315 mm |
|---|---|
| B | 950 mm |
| C | 1430 mm |
| F | 910 mm |
| G | 1015 mm |
| E1 | 1318 mm |
| E2 | 1300 mm |
| E | 3935 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 4315 mm |
|---|---|
| Width | 950 mm |
| Height | 1430 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.