EA-G-345BE9-A01 C
22.90 kW
Defrost: None
Product code: EA-G-445BC9-A01 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 22,493 m³/h |
|---|---|
| Air throw | 22 m |
| External surface | 57.0 m² |
| Inner volume | 29.6 dm³ |
| Fin spacing | 9.0 mm |
| Fin material | Aluminium |
| Net weight | 140 kg |
| Quantity | 4 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 1,960 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 81.0 dB(A) |
| Energy class | E |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| EA-G-445BC9-A01 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 6.71 | 5.96 | ≈ 5.97 | ≈ 5.95 |
| 8 | not rated | not rated | not rated | not rated | 10.90 | ≈ 10.25 | ≈ 16.51 | ≈ 18.68 |
| 10 | not rated | not rated | not rated | not rated | ≈ 15.20 | 22.81 | 25.02 | 27.71 |
| 12 | not rated | not rated | not rated | not rated | not rated | 30.15 | 32.91 | 36.11 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 22.814 | 7.17 | 77.3 |
| A | 3167 mm |
|---|---|
| B | 590 mm |
| C | 675 mm |
| F | 395 mm |
| E1 | 718 mm |
| E2 | 700 mm |
| E | 2835 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 3167 mm |
|---|---|
| Width | 590 mm |
| Height | 675 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.