Skip to Content

Brine cooler EA-G-450AC4-A10 C

Brine cooler EA-G-450AC4-A10 C
Illustrative photo

Producer: Karyer · Line: EA-G (General)

Product code: EA-G-450AC4-A10 C

Cooling capacity i
39.43 kW
Air flow
27,236 m³/h
Fin spacing
4.2 mm
Air throw
22 m
Fans
4 × ⌀500 mm

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Data

Coil
Air flow 27,236 m³/h
Air throw 22 m
External surface 138.0 m²
Inner volume 31.7 dm³
Fin spacing 4.2 mm
Fin materialAluminium
Net weight 178 kg
Fans
Quantity 4
Diameter 500 mm
Speed 1,360 rpm
Power 2,760 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 63.0 dB(A)
Sound power 86.0 dB(A)
Energy class E
Connections
Inlet 2"
Outlet 2"
Defrost
EA-G-450AC4-A10 C None

Performance

Fluid -10 → -7 °C

ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.

ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)

Cooling capacity · High speed (Δ)
39.432 kW Sensible capacity 28.713 kW Fluid flow 12.39 m³/h Pressure drop 99.8 kPa above the recommended pressure drop
Cooling capacity · Low speed (Y)
33.866 kW Sensible capacity 24.598 kW Fluid flow 10.63 m³/h Pressure drop 76.2 kPa above the recommended pressure drop

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K

ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

≈ 1.23 estimate — vendor data irregular here

High speed (Δ)

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K
ΔT [K] \ air [°C] -25-20-15-10-50510
6 not rated not rated not rated not rated 7.87 ≈ 7.97 ≈ 8.04 ≈ 13.98
8 not rated not rated not rated not rated ≈ 13.24 ≈ 22.83 ≈ 28.46 ≈ 31.56
10 not rated not rated not rated not rated ≈ 35.41 39.43 43.11 47.99
12 not rated not rated not rated not rated not rated 52.77 57.50 63.41

Low speed (Y)

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K
ΔT [K] \ air [°C] -25-20-15-10-50510
6 not rated not rated not rated not rated 7.50 7.50 ≈ 7.56 ≈ 7.59
8 not rated not rated not rated not rated 12.54 ≈ 12.07 ≈ 23.97 ≈ 27.52
10 not rated not rated not rated not rated ≈ 17.88 33.87 37.54 41.95
12 not rated not rated not rated not rated not rated 45.68 50.11 55.38

Nominal rating

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Fan connection Cooling capacity [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 39.432 12.39 99.8
Low speed (Y) 33.866 10.63 76.2

Dimensions

Dimension drawing of EA-G-450AC4-A10 C
Dimension drawing
Dimensions as drawn
A 3787 mm
B 590 mm
C 715 mm
F 510 mm
E1 868 mm
E2 850 mm
E 3435 mm
D IN 2"
D OUT 2"
Overall [mm]
Length 3787 mm
Width 590 mm
Height 715 mm

Downloads